2016-06-02 08:05:48 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #16051290 |
| 6/1/16 |
| |
| 1) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| SECTIONS C101.4.4 AND C401.2 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 2) PROVIDE AC CALCULATIONS FOR THE MINI-SPLITS AND THE |
| SCOP RATING OF AC-5 I N THE IT ROOM- SEE TABLE |
| C403.2.3(10). |
| |
| 3) IT DOES NOT APPEAR THAT ADEQUATE HEATING IS BEING |
| SUPPLIED TO ALL ROOMS AND SPACES BASED ON THE AC |
| CALCULATIONS, AND THE EQUIPMENT SCHEDULES. PLEASE |
| CLARIFY WHY MANY OF THE WT BOXES ARE NOT EQUIIPPED WITH |
| HEAT- REFER TO SECTION 309.1 FBC-14 MECHANICAL. |
| |
| 4) TYPE II HEAT HOODS ARE REQUIRED FOR THE CONVECTION |
| OVENS IN THE CAFE- SEE SECTION 507.2.2 AND REVISE THE |
| PLAN ACCORDINGLY. SEE ALSO TABLE 6-4 ASHRAE 62.1- 2010 |
| WHICH REQUIRES AN EXHAUST RATE OF 0.30 CFMS PER SF. |
| FPOR KITCHENETTES. |
| |
| 5) THE EXHAUST DUCT FROM THE JANITOR'S CLOSET SHALL NOT |
| CONNECT INTO THE MAIN DUCT SERVING THE RESTROOMS- |
| SECTION 501.2 |
| |
| 6) THE RESTOOM EXHAUST FANS MUST HAVE A MINIMUM |
| CAPACITY OF 140 CFMS EACH IN ACCORDANCE WITH TABLE |
| 403.3. |
| |
| 7) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE |
| MULTI- FUNCTION ROOM, AND CLARIFY THE NEED FOR THE |
| EXHAUST SYSTEM IN THE ROOM (WHAT WORK IS BEING |
| CONDUCTED IN THE ROOM THAT REQUIRES EXHAUST?). SHOW THE |
| EXHAUST DUCT RUN AND TERMINATION LOCATION. |
| |
| 8) PROVIDE ENGINEERED DETAILS FOR MOUNTING THE OACU-1 |
| CURB TO THE ROOF STRUCTURE AND THE UNIT TO THE CURB- |
| SECTION 301.15. SUBMIT TWO COPIES OF THE MIAMI-DADE NOA |
| FOR THE CONDENSER STANDS APPROVED WITH SIGNATURE BY THE |
| STRUCTURAL EOR. |
| |
| 9) PROVIDE BPD AND WT BOX INSTALLATION DETAILS. |
| |
| 10) PROVIDE SPECIFICATIONS FOR THE CHILLED WATER PIPING |
| AND PIPE INSULATION. |
| |
| 11) SHEET M2.1: FLEX DUCT SIZES NOT SHOWN ON THE PLAN. |
| A) PROVIDE A FIRE DAMPER FOR THE EXHAUST DUCT |
| PENETRATING THE CORRIDOR WALL- SECTION 607.5.2. |
| |
| 12) M7.2: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN |
| AIR DUCT SHOWN IN THE CARRIER CONTROLS DIAGRAM- SECTION |
| 606.2.1. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |