2016-06-02 08:05:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16051290
 6/1/16
  
 1) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTIONS C101.4.4 AND C401.2 FBC-14 ENERGY
 CONSERVATION.
  
 2) PROVIDE AC CALCULATIONS FOR THE MINI-SPLITS AND THE
 SCOP RATING OF AC-5 I N THE IT ROOM- SEE TABLE
 C403.2.3(10).
  
 3) IT DOES NOT APPEAR THAT ADEQUATE HEATING IS BEING
 SUPPLIED TO ALL ROOMS AND SPACES BASED ON THE AC
 CALCULATIONS, AND THE EQUIPMENT SCHEDULES. PLEASE
 CLARIFY WHY MANY OF THE WT BOXES ARE NOT EQUIIPPED WITH
 HEAT- REFER TO SECTION 309.1 FBC-14 MECHANICAL.
  
 4) TYPE II HEAT HOODS ARE REQUIRED FOR THE CONVECTION
 OVENS IN THE CAFE- SEE SECTION 507.2.2 AND REVISE THE
 PLAN ACCORDINGLY. SEE ALSO TABLE 6-4 ASHRAE 62.1- 2010
 WHICH REQUIRES AN EXHAUST RATE OF 0.30 CFMS PER SF.
 FPOR KITCHENETTES.
  
 5) THE EXHAUST DUCT FROM THE JANITOR'S CLOSET SHALL NOT
 CONNECT INTO THE MAIN DUCT SERVING THE RESTROOMS-
 SECTION 501.2
  
 6) THE RESTOOM EXHAUST FANS MUST HAVE A MINIMUM
 CAPACITY OF 140 CFMS EACH IN ACCORDANCE WITH TABLE
 403.3.
  
 7) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE
 MULTI- FUNCTION ROOM, AND CLARIFY THE NEED FOR THE
 EXHAUST SYSTEM IN THE ROOM (WHAT WORK IS BEING
 CONDUCTED IN THE ROOM THAT REQUIRES EXHAUST?). SHOW THE
 EXHAUST DUCT RUN AND TERMINATION LOCATION.
  
 8) PROVIDE ENGINEERED DETAILS FOR MOUNTING THE OACU-1
 CURB TO THE ROOF STRUCTURE AND THE UNIT TO THE CURB-
 SECTION 301.15. SUBMIT TWO COPIES OF THE MIAMI-DADE NOA
 FOR THE CONDENSER STANDS APPROVED WITH SIGNATURE BY THE
 STRUCTURAL EOR.
  
 9) PROVIDE BPD AND WT BOX INSTALLATION DETAILS.
  
 10) PROVIDE SPECIFICATIONS FOR THE CHILLED WATER PIPING
 AND PIPE INSULATION.
  
 11) SHEET M2.1: FLEX DUCT SIZES NOT SHOWN ON THE PLAN.
 A) PROVIDE A FIRE DAMPER FOR THE EXHAUST DUCT
 PENETRATING THE CORRIDOR WALL- SECTION 607.5.2.
  
 12) M7.2: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN
 AIR DUCT SHOWN IN THE CARRIER CONTROLS DIAGRAM- SECTION
 606.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719