Plan Review Notes
Plan Review Notes For Permit 16051290
Permit Number 16051290
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-23 09:00:48INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED
 TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA,
 SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 3. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 4. PER FBC EC 405.7- 50% OF ALL RECEPTACLES 125V, 15
 AND 20A MUST BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND
 COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN
 MODULAR PARTITIONS. SHOW COMPLIANCE.
 5. PROVIDE A NOTE TO COMPLY WITH TAP RULES ON RISER
 DIAGRAM AT THE INTERIOR OF ELECTRICAL ROOM PER NEC
 240.21. A NOTE WILL SUFFICE.
 6. PLEASE DELETE REFERENCE TO CITY OF MIAMI COMPLIANCE
 AND SHOW WPB COMPLIANCE.
 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  