2016-06-06 15:17:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16051254
 6/6/16
  
 1) TRANSFER DUCTS MUST BE SIZED 1.5 TIMES THE
 CROSS-SECTIONAL AREA OF THE SUPPLY DUCTS ENTERING EACH
 ROOM- SEE SECTION 601.5 AND PROVIDE THE TRANSFER AND
 SUPPLY DUCT SIZES FOR EACH ROOM.
  