Plan Review Notes For Permit 16051254 |
Permit Number |
16051254 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-06 12:07:16 | PERMIT # 16051254 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAIL COMMENTS: | | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | AMENDMENTS. | | | | 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | 3) PERMIT APPLICATION INDICATES "SELECTIVE INTERIOR | | DEMOLITION", HOWEVER ALL WALLS ARE MARKED AS | | "EXISTING". A DEMOLITION SHEET / PLAN HAS NOT BEEN | | PROVIDED. | | | | 4) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWERS' COMMENTS | | HAVE BEEN SATISFIED. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|