Plan Review Notes For Permit 16051254 |
Permit Number |
16051254 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-31 17:12:43 | BLDG MISC 2 | 2016-05-31 14:45:47 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY IF THIS PERMIT IS THE DEMO ONLY OF | | SCOPE SHOWN. IF NOT PLEASE PROVIDE REQUIRED INFORMATION | | ON PLANS REGARDING NEW SCOPE. SHOW LIGHTING CIRCUITS | | DESIGNATIONS, EXISTING OR NEW. PANEL SCHEDULE | | REFLECTING NEW INSTALL OF FIXTURES. PROVIDE ALSO THE | | MINIMUM LIGHTING DENSITIES FOR THE AREA AND LIGHTING | | CONTROLS AS PER FBC ENERGY CONSERVATION C405. ALSO | | CLARIFY EMERGENCY LIGHTING FOR THE AREA SHOWN. FBC | | 107.3.5 MINIMUM CRITERIA PLAN REVIEW. | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|