Plan Review Notes
Plan Review Notes For Permit 16051254
Permit Number 16051254
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-31 17:12:43BLDG MISC 2
2016-05-31 14:45:47INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY IF THIS PERMIT IS THE DEMO ONLY OF
 SCOPE SHOWN. IF NOT PLEASE PROVIDE REQUIRED INFORMATION
 ON PLANS REGARDING NEW SCOPE. SHOW LIGHTING CIRCUITS
 DESIGNATIONS, EXISTING OR NEW. PANEL SCHEDULE
 REFLECTING NEW INSTALL OF FIXTURES. PROVIDE ALSO THE
 MINIMUM LIGHTING DENSITIES FOR THE AREA AND LIGHTING
 CONTROLS AS PER FBC ENERGY CONSERVATION C405. ALSO
 CLARIFY EMERGENCY LIGHTING FOR THE AREA SHOWN. FBC
 107.3.5 MINIMUM CRITERIA PLAN REVIEW.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  