Date |
Text |
2016-06-08 09:03:43 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16051254 |
| ADD: 401 S. DIXIE HWY. SUITE # 1 |
| CONT: IBIS BUILDING CORP. |
| TEL: 561-318-8408 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 08/ 2016 |
| ACTION: DENIED |
| LAST PERMITTED ACTIVITY: 13081030. |
| |
| 1) SHEET LS-1 THE LIFE SAFETY PLAN SHOWS 2 EXIT DOORS |
| TO THE EXTERIOR AND A EXIT ACCESS DOOR TO A FIRE RATED |
| CORRIDOR TO THE REAR OF THE TENANT SPACE. |
| THE REAR EXIT ACCESS DOOR SHOWS A CEILING EXIT |
| DIRECTIONAL LIGHT. THE ARE 2 OTHER EXITS TOWARD THE |
| FRONT OF THE TENANT SPACE, ONE IS A EXIT DISCHARGE DOOR |
| DIRECTLY TO THE SIDEWALK ON DIXIE HWY. THE OTHER DOOR |
| THAT HAS THE CEILING MOUNTED EXIT LIGHT TAKING YOU TO |
| THE SIDE DOOR THAT LEADS TO A FENCED IN AND GATED |
| COURTYARD. IS THE GATE UNLOCKED AND MEET THE |
| REQUIREMENTS FOR AN EGRESS COURT THAT LEADS TO THE |
| PUBLIC WAY? 2014 FBC-B 1027.4.2 & 1027.5. |
| |
| 2) SHEET A2 SHOWS A NEW BREAKROOM WITH SINK. THERE ARE |
| NO DETAILS SHOWING COMPLIANCE WITH: 2014 |
| FBC-ACCESSIBLITY CODE 606.1-5. |
| |
| 3) JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |