Plan Review Notes
Plan Review Notes For Permit 16051235
Permit Number 16051235
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-10 07:45:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16051235
 6/10/16
  
 1) AN AC SYSTEM, EXHAUST FAN, AND MOTORIZED LOUVER ARE
 SHOWN ON SHEET D-01-01- THE CHEMICAL FEED SHELTER
 BUILDING: PLEASE PROVIDE MECHANICAL PLANS INCLUDING:
 A) AC SYSTEM, EXHAUST FAN, AND LOUVER EQUIPMENT
 SCHEDULES
 B) AC LOAD CALCULATIONS
 C) EXHAUST VENTILATION CALCULATIONS
 D) SEQUENCE OF OPERATIONS FOR THE AC, FAN, AND LOUVER
 E) WIIND LOAD ENGINEERING FOR INSTALLATION OF THE FAN
 AND LOUVER.
  
 2) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR THE AIR
 INTAKE LOUVER AS REQUIRED BY SECTION 401.4, AND INTAKE
 OPENING PROTECTION DETAILS PER 401.5. SUBMIT A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVER WITH
 APPROVAL SIGNATURE BY THE DESIGN PROFESSIONAL OF
 RECORD.
  
 3) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR THE FAN
 DISCHARGE AS REQUIRED BY SECTION 501.3.1, AND OPENING
 PROTECTION DETAILS PER 501.3.2. SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE FAN WITH APPROVAL
 SIGNATURE BY THE DESIGN PROFESSIONAL OF RECORD.
  
 4) PLEASE REFER TO SECTION 414.1.3 FBC-14 BUILDING AND
 SUBMIT THE REQUIRED REPORT FOR THE SODIUM HYPOCHLORITE
 AND ALL OTHER CHEMICALS TO BE STORED ON USED FOR
 PROCESSING IN THE BUILDING. PLEASE NOTE THAT A
 HAZARDOUS EXHAUST VENTILATION SYSTEM MAY BE REQUIRED-
 SEE SECTION 510 FBC-14 MECHANICAL FOR CODE
 REQUIREMENTS.
  
 5) PROVIDE SUBMITTALS FOR ALL PROCESS PIPING, VALVES,
 AND FITTINGS WITH SHOP DRAWING APPROVAL SIGNATURES FROM
 THE DESIGN PROFESSIONAL OF RECORD.
  