Date |
Text |
2016-06-23 08:15:39 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT:16051235 |
| ADD: 880 VALLEY FORGE RD. |
| CONT: FLORIDA DESIGN DRILLING CORP. |
| TEL: 561-844-2966 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 23/2016 |
| ACTION: DENIED |
| |
| |
| 1) PLEASE NOTE SHEET S-2 INDICATES UNDER NOTE # 1 THIS |
| IS A PRE-MANUFACTURERED BUILDING. PRE-MANUFACTURED |
| BUILDINGS ARE BUILT AT A PLANT TOTALLY COMPLETE. FOR |
| MANUFACTURERED BUILDINGS (MODULAR)AT A PLANT AND |
| TRANSPORTED COMPLETE TO THE JOBSITE, THEY HAVE TO BE |
| PART OF THE STATE MANUFACTURED BUILDING PROGRAM IN |
| COMPLIANCE WITH : |
| FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF |
| INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION |
| ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION |
| SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF. |
| INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE |
| CONDUCTED BY THOSE THIRD-PARTY AGENCIES |
| |
| THIS BUILDING IS SITE BUILT W/ OFF SITE |
| PRE-MANUFACTURED PANELS. PLEASE CORRECT THE |
| TERMINOLOGY. THE ISSUE WE HAVE WITH THIS BUILDING IS ON |
| SHEET S-1 NOTES INDICATE FABRICATION AND ERECTION |
| DRAWINGS WILL BE PREPARED BY A DELEGATE ENGINEER. |
| |
| WHAT WE ARE NOT GETTING IS THE INSPECTION OF THE STEEL |
| (REBAR) AND EMBEDS IN THE STRUCTURAL WALL AND ROOF |
| PANEL OR PANELS. THIS NEEDS TO BE COMPLETED BY A STATE |
| CERTIFIED BUILDING INSPECTOR WHO HOLDS A BN LICENSE. |
| THIS IS NOT A MODULAR BUILDING UNDER THE STATE PROGRAM. |
| FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF |
| INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION |
| ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION |
| SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF. |
| INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE |
| CONDUCTED BY THOSE THIRD-PARTY AGENCIES FLORIDA ADMIN. |
| CODE CHAPTER 61-41 MANUFACTURERED BUILDINGS. |
| |
| FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW BEFORE BEING SUBMITTED TO |
| THE BUILDING DEPARTMENT. |
| |
| 2) ALL ONSITE WELDING OF EMBEDS TO PANEL SYSTEMS EITHER |
| WALL OR ROOF PANELS WILL NEED TO BE COMPLETED BY A |
| CERTIFIED WELDER, PLEASE PROVIDE PAPERWORK INDICATING |
| THEIR CERTIFICATION. |
| |
| 3) PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (C) PANEL WALLS: WALL LOUVERS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 5) SHEET S2 THE WALL INTERIOR ZONE # 4 PRESSURES ARE IN |
| VULT PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE |
| PRODUCT APPROVALS ARE ALL IN VASD. 2014 FBC-B 1609.3.1 |
| WIND SPEED CONVERSION VULT TO VASD. |
| |
| 6) SHEET S2 SHOWS COMPONENT AND CLADDING PRESSURES FOR |
| THE WALL ZONES BUT THERE ARE NO PRESSURES FOR THE FLAT |
| CONCRETE ROOF ZONES 1, 2 NOR 3. 2014 FBC-B 1603.1.4 |
| WIND DESIGN DATA. PLEASE CONVERT PRESSURES TO VASD. |
| 2014 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |