Plan Review Notes
Plan Review Notes For Permit 16051222
Permit Number 16051222
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-03 14:18:121ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16051222
 6/3/16
  
 1) CLARIFY HOW THE AC SYSTEM WAS SIZED- PROVIDE
 CALCULATIONS.
  
 2 PLEASE REFER TO SECTION 414.1.3 FBC-14 BUILDING AND
 SUBMIT THE REQUIRED REPORT FOR THE SODIUM HYPOCHLORITE
 AND ALL OTHER CHEMICALS TO BE STORED ON USED FOR
 PROCESSING IN THE BUILDING. PLEASE NOTE THAT A
 HAZARDOUS EXHAUST VENTILATION SYSTEM MAY BE REQUIRED-
 SEE SECTION 510 FBC-14 MECHANICAL FOR CODE
 REQUIREMENTS.
  
 3) PROVIDE SUBMITTALS FOR THE SODIUM HYPOCHLORITE TANK,
 AND THE PROCESS PIPING, VALVES, AND FITTINGS WITH SHOP
 DRAWING APPROVAL SIGNATURES FROM THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  