Plan Review Notes
Plan Review Notes For Permit 16051208
Permit Number 16051208
Review Stop P
Sequence Number 3
Notes
Date Text
2016-10-12 13:23:44APPROVED WITH PROVISO
  
 PROVIDE BEFORE FIRST INSPECTION
  
 A APPROVED BY BUILDING DEPARTMENT RISER DIAGRAM
 CONTAINING THE FOLLOWING:
  
 1.PLEASE PROVIDE A COMPLETE RISER DIAGRAM. SHOWING
 EXISTING AND NEW PIPING AND REFLECTING THE FLOOR PLAN.
 PER WPB AMEND TO FBC 107.3.5.3(11)
  
 2. SHOW EXISTING AND NEW PIPING AND NEW TANKLESS HEATER
 ON WATER RISER DIAGRAM. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 3. THE FOLLOWING FIXTURES NEED VENTS, MASTER BATH LAV ,
 KITCHEN SINK ,WASHING MACHINE . PER FBC RES P3101.2.1
  
 4. SHOW THE P-TRAPS ON THE SINKS, SHOWERS, TUBS AND
 WASHING MACHINE. PER WPB AMEND TO FBC 107.2.1
  
 5. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL
 STACK FROM THE SECOND FLOOR. PER FBC RES P3005.2.6
  
  
  
  
  