Plan Review Notes For Permit 16051208 |
Permit Number |
16051208 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-10-12 13:23:44 | APPROVED WITH PROVISO | | | | PROVIDE BEFORE FIRST INSPECTION | | | | A APPROVED BY BUILDING DEPARTMENT RISER DIAGRAM | | CONTAINING THE FOLLOWING: | | | | 1.PLEASE PROVIDE A COMPLETE RISER DIAGRAM. SHOWING | | EXISTING AND NEW PIPING AND REFLECTING THE FLOOR PLAN. | | PER WPB AMEND TO FBC 107.3.5.3(11) | | | | 2. SHOW EXISTING AND NEW PIPING AND NEW TANKLESS HEATER | | ON WATER RISER DIAGRAM. PER WPB AMEND TO FBC | | 107.3.5.3(11) | | | | 3. THE FOLLOWING FIXTURES NEED VENTS, MASTER BATH LAV , | | KITCHEN SINK ,WASHING MACHINE . PER FBC RES P3101.2.1 | | | | 4. SHOW THE P-TRAPS ON THE SINKS, SHOWERS, TUBS AND | | WASHING MACHINE. PER WPB AMEND TO FBC 107.2.1 | | | | 5. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL | | STACK FROM THE SECOND FLOOR. PER FBC RES P3005.2.6 | | | | | | | | | | |
|