Plan Review Notes
Plan Review Notes For Permit 16051208
Permit Number 16051208
Review Stop E
Sequence Number 3
Notes
Date Text
2016-10-12 11:40:23REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO'S ( RED LINED )
  
 1] AFCI PROTECTION REQUIRED PER NEC 210.12(B)
  
 2] TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC
 406.12
  
 3] SMOKE ALARMS REQUIRED PER FBC-R 314 & 315
  
 4] LABEL METER ENCLOSURE "METER MAIN" TO COMPLY WITH
 NEC 230.70[A][1] DISCONNECTING MEANS OF SERVICE
 CONDUCTORS SHALL BE LOCATED AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE.
  
 5] CORRECT GROUNDING DETAILS TO A # 4 CU ELECTRODE
 CONDUCTOR PER TABLE NEC 250.66 AND ADD AN INTERSYSTEM
 BONDING TERMINAL IN ACCORDANCE WITH NEC 250.94
  
 6] OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS. RELOCATE PANEL ON SECOND FLOOR AND
 PROVIDE PROPER WORKING CLEARANCE FOR THE FIRST FLOOR
 PANEL. NEC 240.21(2)(D) & FBC-R_E3405 WORKING CLEARANCE
 3' ?
  
 7] PLEASE TRY TO DARKEN IN THE ELECTRICAL POINTS ON THE
 FLOOR PLAN FOR THE QUALITY OF THE EXAMINER REVIEW.
 FBC-107 MINIMUM PLAN REVIEW
  
 - PERMIT # 16051208, 523 28TH STREET WPB FLORIDA. [
 REAR BUILDING ]