Plan Review Notes For Permit 16051208 |
Permit Number |
16051208 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-09-13 06:16:55 | 2ND REVIEW | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | PLUMBING COMMENTS: DUE TO NEW DRAWING BEING SUBMITTED | | THE FOLLOWING DEFICIENCIES IN THE PLANS WERE FOUND | | | | 1.PLEASE PROVIDE A COMPLETE RISER DIAGRAM. SHOWING | | EXISTING AND NEW PIPING AND REFLECTING THE FLOOR PLAN. | | PER WPB AMEND TO FBC 107.3.5.3(11) | | | | 2. SHOW EXISTING AND NEW PIPING AND NEW TANKLESS HEATER | | ON WATER RISER DIAGRAM. PER WPB AMEND TO FBC | | 107.3.5.3(11) | | | | 3. THE FOLLOWING FIXTURES NEED VENTS, MASTER BATH LAV , | | KITCHEN SINK ,WASHING MACHINE . PER FBC RES P3101.2.1 | | | | 4. SHOW THE P-TRAPS ON THE SINKS, SHOWERS, TUBS AND | | WASHING MACHINE. PER WPB AMEND TO FBC 107.2.1 | | | | 5. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL | | STACK FROM THE SECOND FLOOR. PER FBC RES P3005.2.6 | | | | | | | | | | | | NEW DRAWINGS SUBMITTED. | 2016-08-29 17:26:30 | NEW DRAWINGS SUBMITTED. |
|