Plan Review Notes For Permit 16051208 |
Permit Number |
16051208 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-08-17 14:05:42 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1) ORIGINAL PLANS WERE PASSED WITH SEVERAL PROVISO'S | | THAT WEREN'T ADDRESSED IN THE 2ND SUBMITTAL PLEASE ADD | | THE FOLLOWING NOTES: | | 1A) AFCI PROTECTION REQUIRED PER NEC 210.12[B] | | 1B) TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC | | 406.12 | | 1C) SMOKE ALARMS REQUIRED PER FBC-R 314 & 315 | | | | 2) LABEL METER ENCLOSURE "METER MAIN" TO COMPLY WITH | | NEC 230.70[A][1] DISCONNECTING MEANS OF SERVICE | | CONDUCTORS SHALL BE LOCATED AT A READILY ACCESSIBLE | | LOCATION NEAREST THE POINT OF ENTRANCE. | | | | 3) CORRECT GROUNDING DETAILS TO A # 4 CU ELECTRODE | | CONDUCTOR PLUS AUGMENTATE A ROD OR COMPLY WITH PROVING | | 25 OHMS TO GROUND. NEC 250.56. ADD AN INTERSYSTEM | | BONDING TERMINAL IN ACCORDANCE WITH NEC 250.94 | | | | 4) OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE | | VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN | | CLOTHES CLOSETS. RELOCATE PANEL ON SECOND FLOOR AND | | PROVIDE PROPER WORKING CLEARANCE FOR THE FIRST FLOOR | | PANEL. NEC 240.21[D] & 110.26 | | | | 5) PLEASE TRY TO DARKEN IN THE ELECTRICAL POINTS ON THE | | FLOOR PLAN FOR THE QUALITY OF THE EXAMINER REVIEW. | | FBC-107 MINIMUM PLAN REVIEW | | | | - PERMIT # 16051208, 523 28TH STREET WPB FLORIDA. [ | | REAR BUILDING ] |
|