Plan Review Notes For Permit 16051207 |
Permit Number |
16051207 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-10-12 11:15:38 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S ( RED-LINED ) | | | | 1] AFCI PROTECTION REQUIRED PER NEC 210.12(B) | | | | 2] TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC | | 406.12 | | | | 3] SMOKE ALARMS REQUIRED PER FBC-R 314 & 315 | | | | 4] LABEL METER ENCLOSURE "METER MAIN" TO COMPLY WITH | | NEC 230.70[A][1] DISCONNECTING MEANS OF SERVICE | | CONDUCTORS SHALL BE LOCATED AT A READILY ACCESSIBLE | | LOCATION NEAREST THE POINT OF ENTRANCE. | | | | 5] CORRECT GROUNDING DETAILS TO A # 4 CU ELECTRODE | | CONDUCTOR PER TABLE NEC 250.66 AND ADD AN INTERSYSTEM | | BONDING TERMINAL IN ACCORDANCE WITH NEC 250.94 | | | | 4) CLARIFY PANEL LOCATION ? IS IT IN A CLOTHES CLOSET ? | | DOES THE WORKING SPACE HEIGHT SUFFICE THE 6.5' FROM | | FLOOR REQUIREMENT ? NEC 240.24(2)(D) & FBC-R SECTION | | E3405 WORKING CLEARANCE | | | | 5) PLEASE TRY TO DARKEN IN THE ELECTRICAL POINTS ON THE | | FLOOR PLAN FOR THE QUALITY OF THE EXAMINER REVIEW. | | FBC-107 MINIMUM PLAN REVIEW | | | | - PERMIT # 16051207, 523 28TH STREET WPB FLORIDA. [ | | FRONT BUILDING ] |
|