Plan Review Notes
Plan Review Notes For Permit 16051207
Permit Number 16051207
Review Stop E
Sequence Number 3
Notes
Date Text
2016-10-12 11:15:38REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S ( RED-LINED )
  
 1] AFCI PROTECTION REQUIRED PER NEC 210.12(B)
  
 2] TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC
 406.12
  
 3] SMOKE ALARMS REQUIRED PER FBC-R 314 & 315
  
 4] LABEL METER ENCLOSURE "METER MAIN" TO COMPLY WITH
 NEC 230.70[A][1] DISCONNECTING MEANS OF SERVICE
 CONDUCTORS SHALL BE LOCATED AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE.
  
 5] CORRECT GROUNDING DETAILS TO A # 4 CU ELECTRODE
 CONDUCTOR PER TABLE NEC 250.66 AND ADD AN INTERSYSTEM
 BONDING TERMINAL IN ACCORDANCE WITH NEC 250.94
  
 4) CLARIFY PANEL LOCATION ? IS IT IN A CLOTHES CLOSET ?
 DOES THE WORKING SPACE HEIGHT SUFFICE THE 6.5' FROM
 FLOOR REQUIREMENT ? NEC 240.24(2)(D) & FBC-R SECTION
 E3405 WORKING CLEARANCE
  
 5) PLEASE TRY TO DARKEN IN THE ELECTRICAL POINTS ON THE
 FLOOR PLAN FOR THE QUALITY OF THE EXAMINER REVIEW.
 FBC-107 MINIMUM PLAN REVIEW
  
 - PERMIT # 16051207, 523 28TH STREET WPB FLORIDA. [
 FRONT BUILDING ]