Plan Review Notes
Plan Review Notes For Permit 16051207
Permit Number 16051207
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-17 13:51:43REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) ORIGINAL PLANS WERE PASSED WITH SEVERAL PROVISO'S
 THAT WEREN'T ADDRESSED IN THE 2ND SUBMITTAL PLEASE ADD
 THE FOLLOWING NOTES:
 1A) AFCI PROTECTION REQUIRED PER NEC 210.12[B]
 1B) TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC
 406.12
 1C) SMOKE ALARMS REQUIRED PER FBC-R 314 & 315
  
 2) LABEL METER ENCLOSURE "METER MAIN" TO COMPLY WITH
 NEC 230.70[A][1] DISCONNECTING MEANS OF SERVICE
 CONDUCTORS SHALL BE LOCATED AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE.
  
 3) CORRECT GROUNDING DETAILS TO A # 4 CU ELECTRODE
 CONDUCTOR PLUS AUGMENTATE A ROD OR COMPLY WITH PROVING
 25 OHMS TO GROUND. NEC 250.56. ADD AN INTERSYSTEM
 BONDING TERMINAL IN ACCORDANCE WITH NEC 250.94
  
 4) CLARIFY PANEL LOCATION ? IS IT IN A CLOTHES CLOSET ?
 DOES THE WORKING SPACE HEIGHT SUFFICE THE 6.5' FROM
 FLOOR REQUIREMENT ? NEC 110.26 WORKING CLEARANCE &
 FBC-R SECTION E3405
  
 5) PLEASE TRY TO DARKEN IN THE ELECTRICAL POINTS ON THE
 FLOOR PLAN FOR THE QUALITY OF THE EXAMINER REVIEW.
 FBC-107 MINIMUM PLAN REVIEW
  
 - PERMIT # 16051207, 523 28TH STREET WPB FLORIDA. [
 FRONT BUILDING ]