2016-08-29 13:37:59MAIN HOUSE:
 RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 ORIGINAL COMMENT:
 1- PROVIDE COMPLIANCE WITH THE EGRESS REQUIREMENTS OF
 BEDROOM #1 SHOWN ON THE FIRST FLOOR PLAN. SPECIFY
 WINDOW TYPE, SIZE AND SILL HEIGHT SEC. R310
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE:
 THE EMERGENCY ESCAPE SHALL OPEN DIRECTLY INTO A PUBLIC
 WAY OR TO A YARD OR COURT THAT OPENS TO A PUBLIC WAY.
 SEE SEC. R310.1 FBC-RESIDENTIAL. THE DOORS SHOWN ON
 FLOOR PLAN DON'T COMPLY. THEY DON'T OPEN INTO A PUBLIC
 WAY OR YARD OR COURT THAT OPENS TO A PUBLIC WAY. REVISE
 PLANS AS REQUIRED.
  
 ORIGINAL COMMENT:
 2- SCOPE OF WORK IS NOT CLEAR. CLEARLY SPECIFY EXTENT
 OF WORK TO BE PERFORMED. WHY SUBMITTING PRODUCT
 APPROVAL FOR SINGLE HUNG WINDOWS. WHAT'S NEW , WHAT'S
 EXISTING, ETC. SEC. 107.2.1 CITY CITY AMENDMENTS.
  
 RESPONSE:
 (1) SCOPE BUILDING NOTE #1 INDICATES "REPAIR DAMAGED
 EXISTING FRAMING AND STUCCO ON EXISTING EXTERIOR WALL".
 NEED TO INDICATE ON PLANS DAMAGED AREAS AND PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE PROPOSED
 REPAIR. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 (2) SCOPE BUILDING NOTE #3 INDICATES "INSTALL NEW
 INTERIOR FRAMING TO CREATE NEW UPSTAIRS BATHROOM
 ATTACHED TO MASTER BEDROOM". PROVIDE COMPLETE FRAMING
 PLANS AND SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 ORIGINAL COMMENTS:
 3- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS
 SHOWING COMPLIANCE WITH SEC. R315 FBC-RESIDENTIAL.
  
 RESPONSE:
 CARBON MONOXIDE ALARMS TO BE INCLUDED IN THE ORIGINAL
 DRAWING. CORRECTIONS BY HAND ON SUBMITTED COPIES ARE
 NOT ALLOWED.
  
 ORIGINAL COMMENT:
 4- PROVIDE THE NAME AND SIGNATURE IN ALL PLANS OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS
  
 RESPONSE:
 STILL MISSING THE NAME OF THE PERSON RESPONSIBLE FOR
 THE DESIGN.
  
 **** PLEASE REMOVE ANY REVISED DRAWING AND INSERT THE
 NEW DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  