Plan Review Notes For Permit 16051150 |
Permit Number |
16051150 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-27 18:43:02 | BUILDING REVIEW COMMENTS TO REVISION SUBMITTED TO | | ADDRESS PROVISO DATED 05/10/16: | | | | ORIGINAL COMMENT: | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | A) NEW OVERHEAD GARAGE DOORS AS SHOWN ON PLANS. | | RESPONSE: NOT ADDRESSED. NO PRODUCT APPROVAL SUBMITTED | | AT THIS TIME. | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | AND DETAILS. | | RESPONSE: OK. | | | | 2- ARCHITECT TO REVIEW/APPROVE PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.34.1 CITY AMENDMENTS. | | RESPONSE: THIS APPLIES TO GARAGE DOORS. NO PRODUCT | | APPROVAL SUBMITTED YET. | | | | ORIGINAL COMMENT: | | 3- PROVIDE COMPLETE FRAMING DETAIL FOR THE INSTALLATION | | OF TWO OVERHEAD GARAGE DOORS INSTEAD OF ONE AS SHOWN ON | | PLANS. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. | | R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014). | | RESPONSE: REVISED DRAWING DOESN'T SPECIFY THE | | STRUCTURAL CONNECTORS OF ALL THE FRAMING MEMBERS OF THE | | NEW GARAGE DOORS. PROVIDE COMPLETE FRAMING DETAILS AND | | SPECIFICATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|