2016-06-02 17:07:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16051142
 ADD: 400 N. FLAGLER DR. SUITE # 805
 CONT: SMART CHOICE CONSTRUCTION INC.
 TEL: 561-317-3600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 02/2016
 ACTION: DENIED
  
 1) SHEET A1 CODE INFORMATION:
  
 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2014
 ALTERATIONS RESIDENTIAL. THE COVERSHEET SHOULD READ THE
 DESIGN IS TO THE 2014 FBC-BUILDING CODE AND THE 2014
 EXISITING BUILDING CODE, THE 2014 FBC-RESIDENTIAL IS
 FOR 1 & 2 FAMILY ONLY NOT A R2 CONDO.
  
 1B) THE PLANS ALSO STATE THE DESIGN: TABLE 601 BUILDING
 TYPE VB. NOTE THIS IS A 24 STORY R2 HIGHRISE. PLEASE
 REFER TO THE 2014 FBC-B TABLE503 AND BUILDING TYPE; IA
 PLEASE CORRECT PLANS.
  
 1C) SCOPE OF WORK DOES NOT INCLUDE ANY REMOVAL AND
 REPLACEMENT OF EXTERIOR DOORS & WINDOWS. SHEET A-2 AND
 A-3 INDICATE THE REMOVAL AND REPLACEMENT OF THESES
 ELEMENTS. 107.2.1.3 .
  
 2) DISCREPANCY IN PLANS, SHEET A2 IS INDICATED AS
 EXISITNG FLOOR PLAN AND SHEET A3 ALSO INDICATES
 EXISITNG FLOOR PLAN BUT APPEARS TO BE PROPOSED
 MODIFICATIONS TO THE R2 CONDOMINIUM. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. APPEARS TO BE A TYPO.
  
 3) SHEET A3 INDICATES NEW EXTERIOR DOOR AND WINDOWS.
 PLEASE PROVIDE PRODUCT APPROVALS FOR COMPLIANCE WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5A) STRUCTURAL DESIGNS, MWFRS & COMPONENTS AND CLADDING
 BY JAIRO GONZALEZ P. E. INDICATE THEY WERE COMPLETED
 FOR AN EXPOSURE C WHERE AS THE JOBSITE LOCATION IS
 CONSIDERED A D EXPOSURE, BOTH TO THE NOTHEAST AND
 SOUTHEAST A VECTOR OR RAY CAN TRAVEL OVER 6,000 FT
 BEFORE HITTING LAND. 2014 FBC-B 1609.4.3 EXPOSURE
 CATEGORIES.EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE
 GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE
 ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES
 THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
  
 5B) THE OTHER ISSUE IS THE CALCULATIONS ARE ALSO TAKEN
 AT 80 FT. THE BUILDING IS A 24 STORY HIGHRISE. THE
 NEGATIVE PRESSURES ARE ALWAYS TAKEN FROM THE ROOF. QH.
 ASCE7-10.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
 STRUCTURAL CALCULATIONS
  