2016-06-02 17:07:22 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16051142 |
| ADD: 400 N. FLAGLER DR. SUITE # 805 |
| CONT: SMART CHOICE CONSTRUCTION INC. |
| TEL: 561-317-3600 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 02/2016 |
| ACTION: DENIED |
| |
| 1) SHEET A1 CODE INFORMATION: |
| |
| 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2014 |
| ALTERATIONS RESIDENTIAL. THE COVERSHEET SHOULD READ THE |
| DESIGN IS TO THE 2014 FBC-BUILDING CODE AND THE 2014 |
| EXISITING BUILDING CODE, THE 2014 FBC-RESIDENTIAL IS |
| FOR 1 & 2 FAMILY ONLY NOT A R2 CONDO. |
| |
| 1B) THE PLANS ALSO STATE THE DESIGN: TABLE 601 BUILDING |
| TYPE VB. NOTE THIS IS A 24 STORY R2 HIGHRISE. PLEASE |
| REFER TO THE 2014 FBC-B TABLE503 AND BUILDING TYPE; IA |
| PLEASE CORRECT PLANS. |
| |
| 1C) SCOPE OF WORK DOES NOT INCLUDE ANY REMOVAL AND |
| REPLACEMENT OF EXTERIOR DOORS & WINDOWS. SHEET A-2 AND |
| A-3 INDICATE THE REMOVAL AND REPLACEMENT OF THESES |
| ELEMENTS. 107.2.1.3 . |
| |
| 2) DISCREPANCY IN PLANS, SHEET A2 IS INDICATED AS |
| EXISITNG FLOOR PLAN AND SHEET A3 ALSO INDICATES |
| EXISITNG FLOOR PLAN BUT APPEARS TO BE PROPOSED |
| MODIFICATIONS TO THE R2 CONDOMINIUM. 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. APPEARS TO BE A TYPO. |
| |
| 3) SHEET A3 INDICATES NEW EXTERIOR DOOR AND WINDOWS. |
| PLEASE PROVIDE PRODUCT APPROVALS FOR COMPLIANCE WITH: |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| |
| 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 5A) STRUCTURAL DESIGNS, MWFRS & COMPONENTS AND CLADDING |
| BY JAIRO GONZALEZ P. E. INDICATE THEY WERE COMPLETED |
| FOR AN EXPOSURE C WHERE AS THE JOBSITE LOCATION IS |
| CONSIDERED A D EXPOSURE, BOTH TO THE NOTHEAST AND |
| SOUTHEAST A VECTOR OR RAY CAN TRAVEL OVER 6,000 FT |
| BEFORE HITTING LAND. 2014 FBC-B 1609.4.3 EXPOSURE |
| CATEGORIES.EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE |
| GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE |
| ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A |
| DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES |
| THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| |
| 5B) THE OTHER ISSUE IS THE CALCULATIONS ARE ALSO TAKEN |
| AT 80 FT. THE BUILDING IS A 24 STORY HIGHRISE. THE |
| NEGATIVE PRESSURES ARE ALWAYS TAKEN FROM THE ROOF. QH. |
| ASCE7-10. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| STRUCTURAL CALCULATIONS |
| |