Plan Review Notes
Plan Review Notes For Permit 16051101
Permit Number 16051101
Review Stop P
Sequence Number 2
Notes
Date Text
2016-07-15 10:57:071) SHT. AD.1.1 IS A DEMOLITION PLAN FOR THE FIRST
 FLOOR. SHT. ALS 1.1 REFERS TO THE 5TH & 6TH FLOORS FOR
 TOILET FACILITIES. WHICH FLOOR IS THIS WORK BEING DONE?
 CLEARLY INDICATE THE FLOOR NUMBER ON EACH OF THE PLAN
 SHEETS THAT HAVE BEEN SUBMITTED. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) IF THE RENOVATIONS ARE BEING DONE ON THE FIRST
 FLOOR, THE SANITARY FACILITIES REQUIRED TO SERVE THE
 TOAT OCCUPANT LOAD OF THE FLOOR SHALL BE LOCATED NOT
 MORE THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED
 TO BE PROVIDED WITH TOILET FACILITIES AND THE PATH OF
 TRAVEL TO SUCH FACILITIES SHALL NOT EXCEED A DISTANCE
 OF 500 FEET. 2014 FPC SEC.403.3.3.
 3) I HAVE REVIEWED THE PLUMBING FIXTURE CALCULATIONS
 AND I HAVE ARRIVED AT THE FOLLOWING NUMBERS: PLEASE
 REVIEW YOUR CALCULATIONS AND COMPARE AND REVISE IF
 NECESSARY. THE ASSEMBLY OCCUPANCY CALCULATIONS FOR THE
 6 TH FLOOR PLUMBING CALCULATIONS ARE CORRECT.
 BUSINESS OCCUPANCY - 5TH FLOOR
 WATER CLOSETS - MALES= 2.88, FEMALES = 2.88
 LAVATORIES - MALES= 2.17, FEMALES= 2.17
  
 6TH FLOOR - BUSINESS OCCUPANCY
 WATER CLOSETS - MALES=2.14, FEMALES = 2.14
 LAVATORIES - MALES = 1.43, FEMALES = 1.43
 4) SHT.A1.1.4 SHOWS THE WALL FINISH IN THE TOILET ROOMS
 TO BE PAINT. WALLS AND PARTITIONS WITHIN TWO FEET OF
 URINALS AND WATER CLOSETS SHALL CCOMPLY WITH 2014 FBC
 SEC.1210.2.2.
 5) SHT.A4.02 - TOILET ROOM ELEVATION - THE BOTTOM OF
 THE REFLECTING EDGE OF MIRRORS SHALL BE A MAXIMUM OF 40
 INCHES ABOVE THE FINISH FLOOR. THE DETAIL SHOWS 3'-6".
 2014 FAC 603.3.
 6) SHOW THE LENGTH AND WIDTH OF THE NEW MEN'S AND
 WOMEN'S ACCESSIBLE TOILET STALLS ON THE ENLARGED PLAN
 ON SHT. A4.02.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  