2016-07-15 10:57:07 | 1) SHT. AD.1.1 IS A DEMOLITION PLAN FOR THE FIRST |
| FLOOR. SHT. ALS 1.1 REFERS TO THE 5TH & 6TH FLOORS FOR |
| TOILET FACILITIES. WHICH FLOOR IS THIS WORK BEING DONE? |
| CLEARLY INDICATE THE FLOOR NUMBER ON EACH OF THE PLAN |
| SHEETS THAT HAVE BEEN SUBMITTED. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 2) IF THE RENOVATIONS ARE BEING DONE ON THE FIRST |
| FLOOR, THE SANITARY FACILITIES REQUIRED TO SERVE THE |
| TOAT OCCUPANT LOAD OF THE FLOOR SHALL BE LOCATED NOT |
| MORE THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED |
| TO BE PROVIDED WITH TOILET FACILITIES AND THE PATH OF |
| TRAVEL TO SUCH FACILITIES SHALL NOT EXCEED A DISTANCE |
| OF 500 FEET. 2014 FPC SEC.403.3.3. |
| 3) I HAVE REVIEWED THE PLUMBING FIXTURE CALCULATIONS |
| AND I HAVE ARRIVED AT THE FOLLOWING NUMBERS: PLEASE |
| REVIEW YOUR CALCULATIONS AND COMPARE AND REVISE IF |
| NECESSARY. THE ASSEMBLY OCCUPANCY CALCULATIONS FOR THE |
| 6 TH FLOOR PLUMBING CALCULATIONS ARE CORRECT. |
| BUSINESS OCCUPANCY - 5TH FLOOR |
| WATER CLOSETS - MALES= 2.88, FEMALES = 2.88 |
| LAVATORIES - MALES= 2.17, FEMALES= 2.17 |
| |
| 6TH FLOOR - BUSINESS OCCUPANCY |
| WATER CLOSETS - MALES=2.14, FEMALES = 2.14 |
| LAVATORIES - MALES = 1.43, FEMALES = 1.43 |
| 4) SHT.A1.1.4 SHOWS THE WALL FINISH IN THE TOILET ROOMS |
| TO BE PAINT. WALLS AND PARTITIONS WITHIN TWO FEET OF |
| URINALS AND WATER CLOSETS SHALL CCOMPLY WITH 2014 FBC |
| SEC.1210.2.2. |
| 5) SHT.A4.02 - TOILET ROOM ELEVATION - THE BOTTOM OF |
| THE REFLECTING EDGE OF MIRRORS SHALL BE A MAXIMUM OF 40 |
| INCHES ABOVE THE FINISH FLOOR. THE DETAIL SHOWS 3'-6". |
| 2014 FAC 603.3. |
| 6) SHOW THE LENGTH AND WIDTH OF THE NEW MEN'S AND |
| WOMEN'S ACCESSIBLE TOILET STALLS ON THE ENLARGED PLAN |
| ON SHT. A4.02. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |
| |