Plan Review Notes
Plan Review Notes For Permit 16051101
Permit Number 16051101
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-10 07:23:251ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16051101
 6/10/11
  
 1) SHEET M0.1: THE DIGITAL SIGNATURE ON THIS SHEET HAS
 A PROCESS ERROR THAT NEEDS TO BE CORRECTED.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. SEE
 SHEET ALS.1.1 CODE DATA AND ADD THE LEVEL OF ALTERATION
 PER THE FLORIDA EXISTING BUILDING CODE 2014.
  
 3) M2.1: PLEASE ENLARGE THE PRINT ON THE VAV BOXES- IT
 APPEARS THAT THE NUMBER ID'S ON THE BOXES DO NOT MATCH
 THE VAV TAG LABELS.
  
 4) M6.1: PROVIDE THE SCOP RATING OF THE NEW CARRIER
 MINI-SPLIT SYSTEM- SEE TABLE C403.2.3(10) FBC-14 ENERGY
 CONSERVATION.
  
 5) SHOW THE LOCATION OF THE ROOFTOP CONDENSER AND
 PROVIDE TIE-DOWN ENGINEERING FOR THE STAND AND THE CU-
 SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER