| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - GENERAL COMMENT, ALL LOW VOLTAGE AND FIRE ALARM SHALL |
| BE SUBMITTED UNDER A SEPARATE PERMIT. |
| - E0.1 ADD A NOTE, NEC 110.16 ARC-FLASH HAZARD WARNING |
| LABELS & NEC 110.24 MAXIMUM AVAILABLE FAULT CURRENT |
| MARKING REQUIRED, BOTH IDENTIFICATIONS SHALL BE |
| SUITABLE FOR THE ENVIRONMENT INVOLVED. |
| - E2.1 NEC 110.26(D) ILLUMINATION SHALL BE PROVIDED FOR |
| ALL WORKING SPACES ABOUT ELECTRICAL EQUIPMENT, |
| SWITCHBOARDS, AND PANELBOARDS. NO LIGHTS SHOWN BY |
| PANELS ? |
| - E3.1 NEC 300.3(C)(1) ALL CONDUCTORS SHALL HAVE AN |
| INSULATION RATING EQUAL TO AT LEAST THE MAXIMUM CIRCUIT |
| VOLTAGE APPLIED TO ANY CONDUCTOR WITHIN THE ENCLOSURE, |
| CABLE, OR RACEWAY. (UNLESS SEPARATED BY BARRIERS IN |
| ACCORDANCE TO NEC 725) APPLIES TO CONFERENCE ROOM TABLE |
| INSTALLATIONS. |
| - E5.1 PROVIDE EXISTING AIC & SCR OF OCPD AND |
| ELECTRICAL APPARATUS PER NEC 110.9,110.10. EXISTING |
| RISER DIAGRAM TO SHOW CONDUIT, WIRE, AND MAIN |
| PROTECTION SIZES FROM BUS-DUCT DISCONNECT TO EXISTING |
| TRANSFORMER. (SHOW TRANSFORMER KVA RATING AS WELL). FBC |
| 107 MINIMUM PLAN CRITERIA. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |