Plan Review Notes
Plan Review Notes For Permit 16051101
Permit Number 16051101
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-09 15:47:26JOB PERMIT NUMBER: 16051101
 JOB ADDRESS: 501 S FLAGLER DR SUITE #600
 WEST PALM BEACH FLORIDA
 DATE: JUNE 9 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - GENERAL COMMENT, ALL LOW VOLTAGE AND FIRE ALARM SHALL
 BE SUBMITTED UNDER A SEPARATE PERMIT.
 - E0.1 ADD A NOTE, NEC 110.16 ARC-FLASH HAZARD WARNING
 LABELS & NEC 110.24 MAXIMUM AVAILABLE FAULT CURRENT
 MARKING REQUIRED, BOTH IDENTIFICATIONS SHALL BE
 SUITABLE FOR THE ENVIRONMENT INVOLVED.
 - E2.1 NEC 110.26(D) ILLUMINATION SHALL BE PROVIDED FOR
 ALL WORKING SPACES ABOUT ELECTRICAL EQUIPMENT,
 SWITCHBOARDS, AND PANELBOARDS. NO LIGHTS SHOWN BY
 PANELS ?
 - E3.1 NEC 300.3(C)(1) ALL CONDUCTORS SHALL HAVE AN
 INSULATION RATING EQUAL TO AT LEAST THE MAXIMUM CIRCUIT
 VOLTAGE APPLIED TO ANY CONDUCTOR WITHIN THE ENCLOSURE,
 CABLE, OR RACEWAY. (UNLESS SEPARATED BY BARRIERS IN
 ACCORDANCE TO NEC 725) APPLIES TO CONFERENCE ROOM TABLE
 INSTALLATIONS.
 - E5.1 PROVIDE EXISTING AIC & SCR OF OCPD AND
 ELECTRICAL APPARATUS PER NEC 110.9,110.10. EXISTING
 RISER DIAGRAM TO SHOW CONDUIT, WIRE, AND MAIN
 PROTECTION SIZES FROM BUS-DUCT DISCONNECT TO EXISTING
 TRANSFORMER. (SHOW TRANSFORMER KVA RATING AS WELL). FBC
 107 MINIMUM PLAN CRITERIA.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  