2016-06-14 13:35:15 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16051101 |
| ADD: 501 S. FLAGLER DR. 6TH FLOOR |
| CONT: ANDERSON MOORE |
| TEL: 561-662-1819 |
| E-MAIL: RKENNEY@AMC_BUILD.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JUNE 14/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET 002 ALS-1-1. UNDER THE HEADING OF CODE DATA: |
| 1A) THE PLANS INDICATE UNDER THE HEADING USE GROUP: A |
| BUSINESS AND ASSEMBLY OCCUPANCY. THE CODE DATA SHEET |
| DOES NOT DECLARE IF THIS TENANCY IS TO BE A MIXED USE |
| OCCUPANCY SEPARATED (FBC-B508.2.4) OR NON-SEPARATED |
| OCCUPANCIES (FBC-B 50508.3). THE ASSEMBLY USAGE IS OVER |
| 10 % OF THE FLOOR PLATE CREATING MIXED USE OCCUPANCY. |
| |
| 1B) WITH THE MIXED USE OCCUPANCY THE CONSTRUCTION TYPE |
| FOR THE BUILDING HAS TO BE REVIEWED AS WELL. THE CODE |
| DATA SHEET LIST THE BUILDING TYPE AS A IIA. FOR THE |
| ASSEMBLY OCCUPANCY A BUILDING CONSTRUCTION TYPE IIA IS |
| GOOD FOR 3 FLOORS + 1 FLOOR FOR A FULL NFPA 13 |
| SPRINKLER SYSTEM. THIS BUILDING TYPE FOR A MINIMUM |
| WOULD BE REQUIRED TO BE A IB NOT A IIB, SEE 2014 FBC-B |
| TABLE 503. |
| |
| 2) SHEET ALS.1.1. PLEASE REVIEW THE DOOR SWING FOR DOOR |
| NUMBERS 622 & 623. THE OCCUPANT LOAD SERVED BY THESE |
| DOORS IS 50 OR MORE REQUIRING THEM TO SWING IN THE |
| DIRECTION OF TRAVEL. 2014 FBC-B 1008.1.2. |
| |
| 3) LETTER FROM GLIDDENSPINA IS FOR SHOWING COMPLIANCE |
| TO THE 2014 ACCESSIBILITY CODE IN REGARDS TO 202.4.1 |
| DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE FEATURES |
| IN THE EVENT OF DISPROPORTIONALITY. THE LETTER LIST |
| SIGNAGE, HARDWARE, CARPET, VCT & TILE OR 20% OF THE |
| CONTRACT VALUE. THE LETTER DOES NOT SHOW WHAT |
| ACCESSIBLE FEATURES WERE MADE TO BE ACCESSIBLE. THE |
| DEMOLITION PAGE SHOWS THE WHOLE FLOOR BEING DEMOLISHED |
| WITH THE EXCEPTION OF THE COMMON AREA RESTROOMS WHICH |
| ARE OUT OF THE TENANT AREA BUILD OUT. PLEASE PROVIDE A |
| LETTER GIVING THE DESCRIPTION OF THE ELEMENT BEING |
| CORRECTED AND THE DOLLAR AMOUNT FOR EACH ACCESSIBLE |
| ELEMENT CORRECTED. THE$41,060.00 IN ACCESSIBLE UPGRADES |
| ARE TO BE SPENT IN THIS ORDER : |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |