Notes |
Date |
Text |
2016-05-31 13:04:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE ADDITION OF THE NEW SPRINKLER HEADS MAY | | NEGATIVELY AFFECT THE EXISTING HYDRAULIC CALCUALTIONS | | AND SYSTEM PERFORMANCE. | | | | PLEASE PROVIDE NEW HYDRAULIC CALCULATIONS INDICATING | | PROPER SYSTEM PERFORMANCE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|