2017-05-19 12:54:26 | 1) SHT. P5.1 - THE STORM WATER RISER SHOWS A 3 INCH |
| HORIZONTAL STORM LINE SERVING 780 SQ. FEET AT AN 1/8 |
| INCH PER FOOT SLOPE.THE MAXIMUM SQUARE FOOTAGE THAT CAN |
| BE SERVED BY A 3 INCH LINE AT AN 1/8 INCH PER FOOT |
| SLOPE IS 657 SQ. FEET. EITHER INCREASE THE SLOPE OF THE |
| PIPE OR INCREASE THE DRAIN TO 4 INCHES.2014 |
| FBC-PLUMBING TABLE 1106.3. |
| 2) SHT. P2.2 - THE FLOOR DRAIN SHOWN IN TOILET ROOM #47 |
| IS NOT SHOWN ON THE SANITARY RISER DIAGRAM. |
| 3) SHT. P0.1 - GREASE TRAP DETAILS - THE GREASE |
| INTERCEPTOR SHALL COMPLY WITH THE CITY OF WPB STANDARD |
| GREASE INTERCEPTOR DRAWING # GS-7. A COPY HAS BEEN |
| PROVIDED IN THE PERMIT FOLDER. THERE ARE NO DIMENSIONS |
| SHOWN ON THE GREASE INTERCEPTOR TO SHOW COMPLIANCE WITH |
| THE DETAIL. WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) SHT. P0.1 - GREASE TRAP DETAILS - THERE IS A NOTE |
| UNDER THE DETAIL STATING THAT THE GREASE TRAP SHALL |
| COMPLY WITH THE CITY OF CORAL SPRINGS REGULATIONS. THIS |
| IS OBVIOUSLY A TYPO. CORRECT THE NOTE TO READ "CITY OF |
| WEST PALM BEACH." |
| 5) THE MOP SINK SHALL CONNECT TO THE GREASE |
| INTERCEPTOR. 2014 FBC-PLUMBING SEC.1003.11003.3.1. |
| 6) A DETAIL / MANUFACTURER'S SPECIFICATION SHEETS SHALL |
| BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW AND |
| APPROVAL PRIOR TO THE INSTALLATION OF THE LAUNDRY |
| INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1. |
| |