2017-05-19 14:25:44 | 1) THE GAS RISER REFERS TO CSST YET THERE IS NO |
| INFORMATION REGARDING THE CSST ON THE PLANS.WICH TABLE |
| FROM THE GAS CODE IS BEING USED TO SIZE THE CSST? NOTE |
| ON THE PLANS WHICH SIZING TABLE IS BEING USED TO SIZE |
| THE CSST SYSTEM. CLARIFY. |
| 2) SHOW ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 3) CLEARLY SHOW ON THE GAS RISER WHERE THE GAS PIPE |
| TRANSITIONS FROM SCH. 40 METALLIC PIPE TO CSST. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 4) SHOW THE DISTANCE FROM EACH REGULATOR TO THE |
| APPLIANCE OR PIECE OF EQUIPMENT SERVED AND THE TYPE OF |
| PIPE MATERIAL AND SIZE. 2014 FBC-FUEL GAS SEC.402.4.3. |
| 5) SUBMIT AN EXPANDED, CLEAR AND LEGIBLE GAS RISER FOR |
| REVIEW. WITH ALL THE DELTAS, CLOUDS AND EVERYTHING ELSE |
| CRAMMED ONTO THE GAS RISER I CANNOT PERFORM A |
| COMPRHENSIVE REVIEW ON THE SYSTEM. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 6) THE PLANS SHOW THE LP TANK AS ABOVE GROUND. HOW IS |
| THE GAS PIPING GETTING TO THE BUILDING? IF ANY PIPE IS |
| BEING RUN UNDERGROUND, SHOW THE TYPE OF PIPE MATERIAL, |
| SIZE, PSI, AND NOTE THE SIZING TABLE USED TO SIZE THE |
| SECTION OF PIPE ON THE PLANS.WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 7) NOTE ON THE PLAN THE LONGEST LENGTH OF PIPING FROM |
| THE LP TANK TO THE MOST REMOTE LINE PRESSURE REGULATOR. |
| THIS DISTANCE IS TO BE USED FOR SIZING THE MEDIUM |
| PRESSURE SYSTEM.2014 FBC-FUEL GAS SEC.402.4.3. |
| 8) SHT. C4.01 SHOWS A 1 1/2 INCH GAS LINE FROM THE LP |
| TANK AND THE GAS RISER SHOWS A 1 INCH LINE. A 1 1/2 |
| INCH LINE IS ALSO SHOWN ON SHT. P3.1. CLARIFY. 2ND |
| REQUEST. |
| |