Date |
Text |
2016-10-15 07:06:10 | 1) A THOROUGH PLUMBING REVIEW COULD NOT BE DONE AS |
| DRAWINGS P3.1, P3.2, P5.1 & P5.2 HAVE NOT BEEN |
| RESUBMITTED. SUBMIT ALL PLUMBING SHEETS LISTED ON |
| DRAWING COV FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1. |
| THE FOLLOWING PLUMBING REVIEW COMMWNTS WILL REMAIN |
| UNTIL THE REQUIRED DRAWINGS ARE SUBMITTED AND A |
| THOROUGH RE-REVIEW IS DONE. |
| 2) SHT. P5.1 - INDICATE THE SLOPE OF THE PIPE FOR THE |
| STORMWATER RISER. COMPLY WITH TABLE 1106.3 OF 2014 FPC. |
| SIZING SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES |
| PER HOUR. |
| 3) CLEARLY SHOW THE PIPE SIZES ON THE STORMWATER RISER. |
| THEY ARE SO SMALL THEY ARE ILLEGIBLE. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 4) SHT.C 401 - SHOW THE SIZE OF THE STORM DRAIN AND |
| SANITARY LINES ON THE CIVIL DRAWING. 2ND REQUEST. THE |
| PIPE SIZES WERE ADDED ON SHEETS P2.1 & P2.2 WHICH WAS |
| NOT IN MY REVIEW COMMENT. |
| 5) SHT. C6.07 - THERE IA A DETAIL FOR AN OIL / SAND |
| SEPARATOR ON THIS SHEET AND A DETAIL ON SHT. P0.1. THE |
| DETAIL ON SHT. P0.1 COMPLIES WITH THE PLUMBING CODE. |
| DELETE THE DETAIL ON SHT. C6.07. 2ND REQUEST. |
| 6) SHT. L3.01 - CONTACT STEPHEN HUNTER AT 561-822-2240 |
| FOR APPROVAL OF THE LOCATION OF THE BACKFLOW PREVENTER |
| FOR THE IRRIGATION SYSTEM. |
| 7) SHT. P 5.1 - CLEARLY SHOW ON THE SANITARY RISER THAT |
| THE WASHING MACHINE DISCHARGES INTO A 3 INCH STACK PER |
| THE 2014 FPC SEC. 406.2. 2ND REQUEST. |
| 8) SHT. 5.1 - BATHROOM #47 - 2ND FLOOR - THE URINAL IS |
| NOT PERMITTED ON A WET VENT PER THE FPC SEC.912.1. 2ND |
| REQUEST |
| 9) SHOW THE LOCATION OF THE REQUIRED LAUNDRY |
| INTERCEPTOR ON THE FLOOR PLAN AND ALSO ON THE SANITARY |
| RISER DIAGRAM. |
| 10) SHT. P 5.2 - LABEL ALL THE FIXTURES ON THE WATER |
| RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 11) SHT.A4.01 - DETAIL 2D - THE TOILET PAPER DISPENSER |
| SHALL BE A MINIMUM OF 7 INCHES AND A MAXIMUM OF 9 |
| INCHES IN FRONT OF THE WATER CLOSET TO THE CENTERLINE |
| OF THE DISPENSER. 2014 FBC-ACCESS. SEC.604.7. |
| 12) SHT.A4.01 - DETAIL 2B - THE SHOWER CONTROLS SHALL |
| BE LOCATED 15 INCHES MAXIMUM FROM THE CENTERLINE OF THE |
| SEAT TOWARD THE SHOWER OPENING. 2014 FBC-ACCESS. SEC. |
| 608.5.1. |
| |