2017-03-13 10:19:49 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16051078 | | 3/13/17 | | | | 1) SHEETS M2.1 & LS-100: FIRE DAMPERS ARE SHOWN FOR | | DUCTS PENETRATING WALLS AT THE TOOL ROOM, MEDICAL | | STORAGE, STORAGE, LIEU OFFICE, AND THE CAPT OFFICE, | | HOWEVER THESE WALLS ARE NOT SHOWN TO BE FIRE-RATED ON | | THE LIFE SAFETY PLAN- PLEASE CLARIFY. | | | | 2) M2.2: THE RESPONSE NARRATIVE IS STATING THAT A DUCT | | SMOKE DETECTOR IS TO BE INSTALLED IN THE RETURN AIR | | SYSTEM OF OARTU-1, HOWEVER THERE IS NO SYUMBOL SHOWN ON | | THE PLAN TO INDICATE THE LOCATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|