Plan Review Notes
Plan Review Notes For Permit 16051078
Permit Number 16051078
Review Stop M
Sequence Number 3
Notes
Date Text
2017-03-13 10:19:493RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16051078
 3/13/17
  
 1) SHEETS M2.1 & LS-100: FIRE DAMPERS ARE SHOWN FOR
 DUCTS PENETRATING WALLS AT THE TOOL ROOM, MEDICAL
 STORAGE, STORAGE, LIEU OFFICE, AND THE CAPT OFFICE,
 HOWEVER THESE WALLS ARE NOT SHOWN TO BE FIRE-RATED ON
 THE LIFE SAFETY PLAN- PLEASE CLARIFY.
  
 2) M2.2: THE RESPONSE NARRATIVE IS STATING THAT A DUCT
 SMOKE DETECTOR IS TO BE INSTALLED IN THE RETURN AIR
 SYSTEM OF OARTU-1, HOWEVER THERE IS NO SYUMBOL SHOWN ON
 THE PLAN TO INDICATE THE LOCATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  