Plan Review Notes
Plan Review Notes For Permit 16051078
Permit Number 16051078
Review Stop G
Sequence Number 3
Notes
Date Text
2017-03-21 07:17:151) A THOROUGH PLUMBING REVIEW COULD NOT BE DONE AS
 DRAWINGS P3.1, P3.2, P5.1 & P5.2 HAVE NOT BEEN
 RESUBMITTED. SUBMIT ALL PLUMBING SHEETS LISTED ON
 DRAWING COV FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1.
 THE FOLLOWING GAS COMMENTS WILL REMAIN UNTIL ALL THE
 PLUMBING SHEETS ARE SUBMITTED FOR REVIEW.
  
 1) SHT. P5.1 - SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, SIZE THE BRANCH LINES FOR
 GWH-2 & GWH-3. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 FROM THE TANK TO THE STEP DOWN REGULATOR AND FROM THE
 STEP DOWN REGULATOR TO THE APPLIANCES. ON THE PLAN PER
 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. SEC. G2413.2.
 . 2ND REQUEST.
  
 3) GAS APPLIANNCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1. THIS IS FOR INFORMATION ONLY.
  
 4) SHT. C4.01 SHOWS A 1 1/2 INCH GAS LINE AND SHT. P5.1
 SHOWS 2 INCH. CLARIFY. 2ND REQUEST.
  
 5) THE GAS SIZING TABLE REFERENCED ON THE GAS RISER IS
 FOR NATURAL GAS AND THIS SYSTEM IS PROPANE THEREFORE A
 COMPRHENSIVE GAS REVIEW COULD NOT BE DONE. PLACE A
 REFERENCE ON THE PLAN TO THE CORRECT SIZING TABLE USED
 FOR THIS SYSTEM.
  
 6) THE GAS RISER SHOWS THE DRYER AS HAVING 35,000 BTU'S
 AND SHT. P0.1 SHOWS 110,000 BTU'S. CLARIFY.
  
 7) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. SHOW
 THIS ON THE GAS RISER. WPB AMEND. TO FBC SEC. 107.2.1.
  
 8) SHT. P5.1 - THE GAS RISER SHOWS THE PRESSURE
 REDUCING FROM 2 PSI TO 0.5 PSI WITHOUT ANY STEP DOWN
 REGULATORS ON THE SYSTEM. SHOW THE LOCATION OF ALL
 STEP-DOWN REGULATORS ON THE RISER.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  