2017-03-23 11:13:16 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16071078 |
| ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| CONT: HEDRICK BROTHERS |
| TEL: 561-662-8049 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 3RD REVIEW |
| DATE: THURS. MARCH 23/ 2017 |
| ACTION: DENIED |
| |
| |
| 1) MISSING DOCUMENTS 2014 FLORIDA BUILDING CODE W 2014 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| |
| 1A) 3RD REQUEST/ SEMI-COMPLIED, ONLY 2 ORIGINAL SIGNED |
| & SEALED SOILS REPORTS WERE PROVIDED. SOILS REPORTS |
| SUBMITTED ARE COPIES THEY DO NOT HAVE THE ENGINEERS |
| ORIGINAL SIGNATURE. SOILS REPORT: 2014 FBC-B 1803.5.2 |
| QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 2) 4/04/2017 BUILDING PROVISO: E-MAILED THE ARCHITECT |
| AND BUILDER THERE IS NO LONGER A NEED FOR A RESIDENT |
| INSPECTOR, I SPOKE WITH TTHE BUILDIJNG OFFICIAL ROBERT |
| BROWN AND WILL REQUIRE THE CONTRACTOR TO PROVIDE WELD |
| PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. |
| 2014 FBC-B 2204.1 WELDING |
| 2014 FBC-B 2204.2 BOLTING |
| |
| 3) SHEET LS-200: 4A) BUILDING PROVISO: WILL BE PROVIDED |
| BY THE CONTRACTOR PRIOR TO CONSTRUCTION AS A SHOP |
| DRAWING. DEFERRED SUBMITTAL. PLEASE PROVIDE THE AREA |
| CONCRETE BLOCK MANUFACTURER THAT WILL BE PROVIDING THE |
| 2 HOUR FIRE RATED BLOCK, IN THE EQUIVALENT THICKNESS |
| PER 2014 FBC-B TABLE 722.3.2. |
| |
| 4) BUILDING PROVISO: SHEET A-102A INDICATES A FIRE |
| RATED CHASE FOR THE RANGE EXHAUST DUCT, THE DETAIL IS |
| FOR SHALT WALL CONSTRUCTION, PLEASE PROVIDE A DETAIL |
| HOW THE BOTTOM OF THE SHAFT WILL BE SEALED OR |
| PENETRATION THROUGH THE RATED FLOOR. 713.11 ENCLOSURE |
| AT THE BOTTOM. SHOP DRAWINGS ARE TO BE SUBMITTED TO THE |
| BUILDING DEPARTMENT INDICATING THE EXACT PRODUCT THAT |
| ARE TO BE INSTALLED. |
| |
| 5) BUILDING PROVISO: DEFERRED SUBMITTALS. MISSING |
| PRODUCT APPROVALS: 2014 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS - FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH |
| OPENING SIZE. |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |