2016-10-14 15:03:541) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. SIZING CALCULATIONS SHALL BE IN ACCORDANCE
 WITH FL. ADMIN. CODE RULE 64E-6.013. 2ND REQUEST.
 2) SHT. P5.1 - INDICATE THE SLOPE OF THE PIPE FOR THE
 STORMWARE RISER. COMPLY WITH TABLE 1106.3 OF 2014 FPC.
 SIZING SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES
 PER HOUR.
 3) CLEARLY SHOW THE PIPE SIZES ON THE STORMWATER RISER.
 THEY ARE SO SMALL THEY ARE ILLEGIBLE. WPB AMEND. TO FBC
 SEC. 107.2.1.