Plan Review Notes
Plan Review Notes For Permit 16051078
Permit Number 16051078
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-09-21 10:09:401718 PARKER AVENUE
 PERMIT #16051078
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 RESPONSE COMMENT: A REVISED SHEET M6.1 WITH ADJUSTED
 EXHAUST FAN CFM WAS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET M6.1: PER NFPA 88A - PARKING
 STRUCTURES SECTION 6.3.1 ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1 FT3/MIN PER FT2 OF
 FLOOR AREA DURING HOURS OF NORMAL OPERATION.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE