2016-09-13 10:55:53 | 2ND REVIEW ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | PENDING COMMENTS: | | | | | | 6. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL | | AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC | | 107.3.5 | | 7. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 | | 10. SHEET E5.1- GROUNDING ELECTRODE CONDUCTOR | | UNDERSIZED AT 2/0. SHOW 3/0 PER TABLE NEC 250.66. ALSO | | CORRECT NOTE 6 TO SHOW 3/0. SHEET NOT INCLUDED ON SET. | | 13. PLEASE CLARIFY THE NON-REQUIRED COPS NOTES PROVIDED | | AS TO AHJ AUTHORIZATION TO EXCLUDE THE REQUIREMENTS OF | | NEC 708 TO THIS PROJECT. PLEASE PROVIDE WHICH AHJ HAS | | GIVEN THIS DETERMINATION, AS THIS FACILITY IS A COPS. | | 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL | | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | REGARDING THIS PROJECT. | | | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|