2016-09-13 10:55:532ND REVIEW ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
  
 6. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC
 107.3.5
 7. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 10. SHEET E5.1- GROUNDING ELECTRODE CONDUCTOR
 UNDERSIZED AT 2/0. SHOW 3/0 PER TABLE NEC 250.66. ALSO
 CORRECT NOTE 6 TO SHOW 3/0. SHEET NOT INCLUDED ON SET.
 13. PLEASE CLARIFY THE NON-REQUIRED COPS NOTES PROVIDED
 AS TO AHJ AUTHORIZATION TO EXCLUDE THE REQUIREMENTS OF
 NEC 708 TO THIS PROJECT. PLEASE PROVIDE WHICH AHJ HAS
 GIVEN THIS DETERMINATION, AS THIS FACILITY IS A COPS.
 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL