Plan Review Notes
Plan Review Notes For Permit 16051078
Permit Number 16051078
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-18 14:01:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071078
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. OCT. 18/ 2016
 ACTION: DENIED
  
 NOTICE TO CONTRACTOR PLANS WILL NOT PASS AS LONG AS THE
 FAILED SHEETS ARE WITHIN THE SET OF DOCUMENTS!!!!!!!!
 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.
  
  
 1) MISSING DOCUMENTS 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION:
 107.3.5.1 COMMERCIAL BUILDINGS:
  
 1A) 2ND REQUEST SOILS REPORTS SUBMITTED ARE COPIES THEY
 DO NOT HAVE THE ENGINEERS ORIGINAL SIGNATURE. SOILS
 REPORT: 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE
 THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE
 SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR
 TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 1B) 2ND REQUEST ENERGY CALCULATIONS: 2014 FBC-ENERGY
 CODE. C401.2 APPLICATION. COMMERCIAL BUILDINGS
 SUBMITTED ANSI/ASHRAE/IESNA 90.1. SEE MECHANICAL
 COMMENT # 5, REVISE ENERGY CALCULATIONS TO INCLUDE CU-1
 & CU-2.
  
 2) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR
 PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
 STEEL WELDED FRAMEWORK (BAR JOIST & ROOF DECK).
 RESPONSE: PER THE BUILDING OFFICIAL ROBERT BROWN,
 SPECIAL INSPECTIONS WILL ONLY BE REQUIRED FOR
 STRUCTURAL STEEL WELDING AND BOLTABLE CONNECTIONS.
  
 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS E-MAILED TO:
 [email protected] 10/18/2016 1:37 PM
  
 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED.
  
 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) SHEET LS-100 & LS-101:
  
 3) COMPLIED.
  
 4) SHEET LS-200:
 4A) BUILDING PROVISO: WILL BE PROVIDED BY THE
 CONTRACTOR PRIOR TO CONSTRUCTION AS A SHOP DRAWING.
 DEFERRED SUBMITTAL. PLEASE PROVIDE THE AREA CONCRETE
 BLOCK MANUFACTURER THAT WILL BE PROVIDING THE 2 HOUR
 FIRE RATED BLOCK, IN THE EQUIVALENT THICKNESS PER 2014
 FBC-B TABLE 722.3.2.
  
 4B) COMPLIED
  
 5)COMPLIED. ASCE 24-05 FOR ESSENTIAL FACILITIES TABLE
 1-1 FIRE STATIONS A BUILDING CATEGORY IV. TABLE 2-1 FOR
 CATEGORY IV STRUCTURES REQUIRES A ELEVATION OF BFE(BASE
 FLOOD ELEVATION)+ 2 FT. THE PROPOSED NEW BASE FLOOD
 ELEVATION OF 12.7 FT. + 2.0 FT= 14.7 FT. NGVD AS THE
 MINIMUM BUILDING HEIGHT. THE NEW PROPOSED SLAB HEIGHT
 OF 15.53 FT. NGVD IS CODE COMPLIANT TO THE MORE
 STRINGENT ASCE 24-5.
  
 6A-B) COMPLIED.
  
 6C) NEW COMMENT THE DORM ROOMS SHOW STOREFRONT WINDOWS.
 IN DISCUSSION WITH THE BUILDING OFFICIAL ROBERT BROWN
 RATHER THAN REQUEST COMPLIANCE WITH 2014 FBC-B 1029
 EMERGENCY ESCAPE AND RESCUE WINDOWS THIS R2 OCCUPANCY
 IS SIMILAR TO SLEEPING ROOMS FOR SLEEP STUDIES AND OR
 I-2 OCCUPANCIES WHERE THE INDIVIDUALS ARE MONITORED OR
 SUPERVISION. ON SHEET LS-100 UNDER THE WORDING DORM
 THERE IS A REVISION # 1 BUBBLED R-2 OCCUPANCY, PLEASE
 ADD THE VERBIAGE, UNDER MONITORED WATCH PERSONAL.
  
 7-10)COMPLIED.
  
 10) BUILDING PROVISO: SHEET A-102A INDICATES A FIRE
 RATED CHASE FOR THE RANGE EXHAUST DUCT, THE DETAIL IS
 FOR SHALT WALL CONSTRUCTION, PLEASE PROVIDE A DETAIL
 HOW THE BOTTOM OF THE SHAFT WILL BE SEALED OR
 PENETRATION THROUGH THE RATED FLOOR. 713.11 ENCLOSURE
 AT THE BOTTOM. SHOP DRAWINGS ARE TO BE SUBMITTED TO THE
 BUILDING DEPARTMENT INDICATING THE EXACT PRODUCT THAT
 ARE TO BE INSTALLED.
  
 11) COMPLIED ICC-ES REPORT ESR- ICYNENE.
  
 12) COMPLIED. PRESSURES ARE FOUND ON SHEETS A-201 &
 S-401
  
 13) BUILDING PROVISO: DEFERRED SUBMITTALS. MISSING
 PRODUCT APPROVALS: 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS - FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 14-15) COMPLIED.
  
 16A)SEMI-COMPLIED/ 2ND REQUEST. SHEETS A-403A ( A-405
 COMPLIED) SHOWS THE HANDRAIL STARTING A HORIZONTAL
 EXTENSION AT THE FIRST RISER CAUSING THE EXTENSION TO
 BE AT 3 FT. 6 INCHES IN HEIGHT. NOTE IN THE FBC-B
 SECTION 1012.6 THE HANDRAIL SHALL CONTINUE ITS SLOPE
 PAST THE 1ST RISE THE DISTANCE OF THE TREAD BEFORE THE
 12 INCH HORIZONTAL EXTENSION STARTS. THE HANDRAIL
 DEPICTED AT THE TOP OF THE STAIR AT 3 FEET ABOVE THE
 FINISH FLOOR WILL END UP AT 3 FOOT ABOVE THE FINISH
 FLOOR NOT THE 3 FOOT- 6 INCHES AS SHOWN.
  
 16B-C) COMPLIED.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  