2016-10-18 14:01:25 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16071078 |
| ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| CONT: HEDRICK BROTHERS |
| TEL: 561-662-8049 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: TUES. OCT. 18/ 2016 |
| ACTION: DENIED |
| |
| NOTICE TO CONTRACTOR PLANS WILL NOT PASS AS LONG AS THE |
| FAILED SHEETS ARE WITHIN THE SET OF DOCUMENTS!!!!!!!! |
| 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. |
| |
| |
| 1) MISSING DOCUMENTS 2014 FLORIDA BUILDING CODE W 2014 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| |
| 1A) 2ND REQUEST SOILS REPORTS SUBMITTED ARE COPIES THEY |
| DO NOT HAVE THE ENGINEERS ORIGINAL SIGNATURE. SOILS |
| REPORT: 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE |
| THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE |
| SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR |
| TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 1B) 2ND REQUEST ENERGY CALCULATIONS: 2014 FBC-ENERGY |
| CODE. C401.2 APPLICATION. COMMERCIAL BUILDINGS |
| SUBMITTED ANSI/ASHRAE/IESNA 90.1. SEE MECHANICAL |
| COMMENT # 5, REVISE ENERGY CALCULATIONS TO INCLUDE CU-1 |
| & CU-2. |
| |
| 2) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR |
| PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 |
| POUNDS PER SQUARE INCH |
| 4. FOR PILE DRIVING |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION |
| STEEL WELDED FRAMEWORK (BAR JOIST & ROOF DECK). |
| RESPONSE: PER THE BUILDING OFFICIAL ROBERT BROWN, |
| SPECIAL INSPECTIONS WILL ONLY BE REQUIRED FOR |
| STRUCTURAL STEEL WELDING AND BOLTABLE CONNECTIONS. |
| |
| 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. FORMS E-MAILED TO: |
| [email protected] 10/18/2016 1:37 PM |
| |
| 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. |
| |
| 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 3) SHEET LS-100 & LS-101: |
| |
| 3) COMPLIED. |
| |
| 4) SHEET LS-200: |
| 4A) BUILDING PROVISO: WILL BE PROVIDED BY THE |
| CONTRACTOR PRIOR TO CONSTRUCTION AS A SHOP DRAWING. |
| DEFERRED SUBMITTAL. PLEASE PROVIDE THE AREA CONCRETE |
| BLOCK MANUFACTURER THAT WILL BE PROVIDING THE 2 HOUR |
| FIRE RATED BLOCK, IN THE EQUIVALENT THICKNESS PER 2014 |
| FBC-B TABLE 722.3.2. |
| |
| 4B) COMPLIED |
| |
| 5)COMPLIED. ASCE 24-05 FOR ESSENTIAL FACILITIES TABLE |
| 1-1 FIRE STATIONS A BUILDING CATEGORY IV. TABLE 2-1 FOR |
| CATEGORY IV STRUCTURES REQUIRES A ELEVATION OF BFE(BASE |
| FLOOD ELEVATION)+ 2 FT. THE PROPOSED NEW BASE FLOOD |
| ELEVATION OF 12.7 FT. + 2.0 FT= 14.7 FT. NGVD AS THE |
| MINIMUM BUILDING HEIGHT. THE NEW PROPOSED SLAB HEIGHT |
| OF 15.53 FT. NGVD IS CODE COMPLIANT TO THE MORE |
| STRINGENT ASCE 24-5. |
| |
| 6A-B) COMPLIED. |
| |
| 6C) NEW COMMENT THE DORM ROOMS SHOW STOREFRONT WINDOWS. |
| IN DISCUSSION WITH THE BUILDING OFFICIAL ROBERT BROWN |
| RATHER THAN REQUEST COMPLIANCE WITH 2014 FBC-B 1029 |
| EMERGENCY ESCAPE AND RESCUE WINDOWS THIS R2 OCCUPANCY |
| IS SIMILAR TO SLEEPING ROOMS FOR SLEEP STUDIES AND OR |
| I-2 OCCUPANCIES WHERE THE INDIVIDUALS ARE MONITORED OR |
| SUPERVISION. ON SHEET LS-100 UNDER THE WORDING DORM |
| THERE IS A REVISION # 1 BUBBLED R-2 OCCUPANCY, PLEASE |
| ADD THE VERBIAGE, UNDER MONITORED WATCH PERSONAL. |
| |
| 7-10)COMPLIED. |
| |
| 10) BUILDING PROVISO: SHEET A-102A INDICATES A FIRE |
| RATED CHASE FOR THE RANGE EXHAUST DUCT, THE DETAIL IS |
| FOR SHALT WALL CONSTRUCTION, PLEASE PROVIDE A DETAIL |
| HOW THE BOTTOM OF THE SHAFT WILL BE SEALED OR |
| PENETRATION THROUGH THE RATED FLOOR. 713.11 ENCLOSURE |
| AT THE BOTTOM. SHOP DRAWINGS ARE TO BE SUBMITTED TO THE |
| BUILDING DEPARTMENT INDICATING THE EXACT PRODUCT THAT |
| ARE TO BE INSTALLED. |
| |
| 11) COMPLIED ICC-ES REPORT ESR- ICYNENE. |
| |
| 12) COMPLIED. PRESSURES ARE FOUND ON SHEETS A-201 & |
| S-401 |
| |
| 13) BUILDING PROVISO: DEFERRED SUBMITTALS. MISSING |
| PRODUCT APPROVALS: 2014 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS - FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH |
| OPENING SIZE. |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 14-15) COMPLIED. |
| |
| 16A)SEMI-COMPLIED/ 2ND REQUEST. SHEETS A-403A ( A-405 |
| COMPLIED) SHOWS THE HANDRAIL STARTING A HORIZONTAL |
| EXTENSION AT THE FIRST RISER CAUSING THE EXTENSION TO |
| BE AT 3 FT. 6 INCHES IN HEIGHT. NOTE IN THE FBC-B |
| SECTION 1012.6 THE HANDRAIL SHALL CONTINUE ITS SLOPE |
| PAST THE 1ST RISE THE DISTANCE OF THE TREAD BEFORE THE |
| 12 INCH HORIZONTAL EXTENSION STARTS. THE HANDRAIL |
| DEPICTED AT THE TOP OF THE STAIR AT 3 FEET ABOVE THE |
| FINISH FLOOR WILL END UP AT 3 FOOT ABOVE THE FINISH |
| FLOOR NOT THE 3 FOOT- 6 INCHES AS SHOWN. |
| |
| 16B-C) COMPLIED. |
| |
| 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |