2016-06-13 13:30:021) SUBMIT SPECIFICATIONS FOR THE GENERATOR, FUEL
 TANK,AND PIPING DETAILS. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SEPARATE PERMITS WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTERS.
 3) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR.
 4) SUBMIT A STORM WATER RISER DIAGRAM. SHOW THE SQUARE
 FOOTAGE DRAINED BY EACH DRAIN. THE SIZING SHALL INCLUDE
 ONE-HALF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF. COMPLY WITH 2014 FPC TABLE
 1106.3 & 1106.2 (2), SEC.1106.4.
 5) SHT. C4.01 - SHOW THE SIZE OF THE STORM DRAIN AND
 SANITARY LINES ON THE PLAN.WPB AMEND. TO FBC SEC.
 107.2.1.
 6) SHT. C6.07 - THERE IS A DETAIL FOR AN OIL AND
 SEPARATOR ON THIS SHEET AND A DETAIL ON SHT. P0.1. THE
 DETAIL ON SHT. P0.1 COMPLIES WITH THE PLUMBING CODE.
 DELETE THE DETAIL ON C6.07.
 7) SHT. C6.05 - A SAMPLING PORT IS REQUIRED ON THE
 DISCHARGE LINE FROM THE GREASE INTERCEPTOR AND THE OIL
 SEPARATOR.
 8) SHT. L3.01 - THE BACKFLOW PREVENTER FOR THE
 IRRIGATION SYSTEM SHALL BE LOCATED AS CLOSE AS POSSIBLE
 TO THE METER PER THE CITY'S CROSS CONNECTION MANUAL.
 YOU MAY CONTACT UTILITITES AT 822-2240 FOR FURTHER
 DIRECTION.
 9) THE LANDSCAPE/IRRIGATION PLANS ARE STAMPED "NOT FOR
 CONSTRUCTION". CLARIFY.
 10) SHT. A1.04 - SHOW THE DISTANCE OF THE WATER HEATER
 EXHAUST FROM THE RANGE HOOD SUPPLY FAN AND ALSO FROM
 THE WATER HEATER INTAKE. SUBMIT DOCUMENTATION FROM THE
 MANUFACTURER SHOWING THESE MINIMUM REQS.ALSO, SEE SEC.
 503.2.3 & 503.8 OF 2014 FGC.
 11) SHT. A-400 - DETAIL #1 - THE CENTER TO CENTER
 MEASUREMENT BETWEEN THE URINAL AND THE LAVATORY SHALL
 BE A MINIMUM OF 30 INCHES. 2014 FPC SEC.405.3.1.
 12) SHT. A-400 - DETAIL #1C & SHT.A-401 DETAIL 2D - THE
 TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES FROM
 THE THE FRONT OF THE TOILET BOWL TO THE CENTER OF THE
 DISPENSER. 2014 FAC SEC. 604.7.
 13) SHT. A-400 - THE HANDICAPPED ACCESSIBLE TOILET SEAT
 HEIGHT SHALL BE 17-19 INCHES ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE SEAT. SEE ELEVATION 1C.
 14) IF THE ADA BATHING ROOM ON THE SECOND FLOOR IS TO
 BE UNISEX, IT SHALL NOT CONTAIN A URINAL. FAC
 SEC.213.2.1.
 15) THIS BUILDING CONSISTS OF FOUR DIFFERENT OCCUPANCY
 TYPES: ASSEMBLY,BUSINESS, R-2 ( DORMITORY) AND S-2.
 PLACE ALL FOUR OCCUPANCIES ON THE PLANS AND THE
 OCCUPANT LOAD FOR EACH AREA.
 16) SUBMIT INFORMATION AS TO WHAT TYPE OF ITEMS WILL BE
 STORED IN THE SUPPLY STORAGE ROOM.SHT. A-100 INDICATES
 A REINSTALLED COMPRESSOR.SUBMIT A COMPRESSED AIR RISER
 FOR REVIEW IF ANY HARD PIPING WILL BE INSTALLED.
 17) THE WASHER & DRYER IN LAUNDRY ROOM # 51 SHALL
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY SEC. 611.
 18)THE ICE MACHINE SHALL BE PROVIDED WITH A BACKFLOW
 PREVENTER PERR 2014 FPC SEC.608.3.
 19) THE BATHROOMS IN THE CAPTAIN'S AND LIEUTENANT'S
 DORM ROOM SHALL COMPLY WITH 2014 FAC SEC.213.2.
 20) SHT. A-401 - ADA RESTROOM #38 - THE LOCATION AND
 HEIGHT OF THE SHOWER CONTROLS SHALL COMPLY WITH 2014
 FAC SEC.608.5.1.
 21) SHT. A-700 - THE WALLS AND PARTITIONS WITHIN 2 FEET
 OF OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 CCOMPLY WITH FBC SEC.1210.2.2.
 22) SHT. P0.1 - INDICATE THE SIZE/CAPACITY OF THE
 EXPANSION TANK ON THE WATER HEATER DETAIL.
 23) SHT. P0.1 - THE SHOWER IN THE DECON ROOM IS LABELED
 AS A HANDICAPPED SHOWER. CLARIFY.
 24) SUBMIT AN EXPANDED WATER RISER DIAGRAM.THE PIPE
 SIZES ARE ILLEGIBLE.CLEARLY SIZE THE WATER LINES.
 25) P5.1 - SIZE THE FLOOR DRAIN, SHOWER AND FLOOR SINK
 IN THE DECON ROOM.
 26) SHT. P5.1 - FIRST FLOOR ADA RESTROOM (#3) & STAFF
 RESTROOM (#11) SHOWS A URINAL ON A WET VENT. ONLY
 FIXTURES WITHIN A BATHROOM GROUP ARE PERMITTED ON A WET
 VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP" IN
 CHAPTER 2, DEFINITIONS OF THE PLUMBING CODE.
 27) THE WASHING MACHINE IS NOT SHOWN ON THE SANITARY
 RISER DIAGRAM.THE WASTE STACK SHAL BE A MINIMUM OF 3
 INCHES PER 2014 FPC SEC.406.2.
 28) BATHROOM # 47 - 2ND FLOOR - THE URINAL IS NOT
 PERMITTED ON A WET VENT. ONLY FIXTURES WITHIN A
 BATHROOM GROUP ARE PERMITTED ON A WET VENT. REFER TO
 THE DEFINITION OF "BATHROOM GROUP" IN CHAPTER 2,
 DEFINITIONS OF THE PLUMBING CODE.
 29) THE OIL SEPARATOR IS LABELED AS A GREASE TRAP ON
 THE SANITARY RISER DIAGRAM. PLEASE CORRECT.
 30) 2ND FLOOR ADA RESTROOM (38) - THE SHOWER SHALL BE
 INDIVIDUALLY VENTED.
 31) 2ND FLOOR ADA RESTROOM (38) - THE LAVATORY IS NOT
 VENTED.
 32) A LAUNDRY INTERCEPTOR IS REQUIRED PER 2014 FPC
 SEC.1003.6.
  
  
 PLUMBING PLAN REVIEW