2016-06-15 10:12:511) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. THE
 PIPE SIZES ARE ILLEGIBLE, THEY ARE TOO SMALL TO READ.
  
 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 FROM THE TANK TO THE STEP DOWN REGULATOR AND FROM THE
 STEP DOWN REGULATOR TO THE APPLIANCES. ON THE PLAN PER
 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. SEC. G2413.2.
 .
  
 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER
 PER 2014 FGC SEC.304.1.
  
 4) GAS APPLIANNCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1.
  
 5) SHT. C4.01 SHOWS A ONE INCH GAS LINE AND SHT. P5.1
 APPEARS TO SHOW A DIFFERENT SIZE. CLARIFY.
  
 6) SHT. C4.01 REFRES TO AN UNDERGROUND LP TANK BUT SHT.
 P3.1 APPEARS TO SHOW AN ABOVEGROUND TANK. CLARIFY.
  
 7) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
  
 8) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 9) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED
 PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK
 SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT
 WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 10) SHT.P5.1 - DELETE THE REFERENCE TO THE 2004 EDITION
 OF THE FBC. THE CODE IN EFFECT IS THE 2014 EDITION.
  
 11) PLEASE CHECK BTU LOAD ON THE SYSTEM.I HAVE
 CALCULATED A DIFFERENT BTU LOAD.
  
  