2016-07-02 10:08:17INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL CODE REFERENCES SHOWN ON SHEET E.01 TO
 SHOW FLORIDA BUILDING CODE 2014 5TH EDITION AND AS
 STATED ABOVE.
 2. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL
 SUFFICE.
 3. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR GENERATOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE
 AND DATA, SIGNAGE, WIRELESS SYSTEMS, TRUCK CHARGING
 STATIONS, ETC. A NOTE WILL SUFFICE.
 4. PLEASE LABEL RECEPTACLE IN TO BE GFCI PROTECTED PER
 NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI.
 5. PLEASE LABEL RECEPTACLE IN KITCHEN ALL TO BE GFCI
 PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK, ALL
 TO BE GFCI.
 6. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC
 107.3.5
 7. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 8. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 9. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 10. SHEET E5.1- GROUNDING ELECTRODE CONDUCTOR
 UNDERSIZED AT 2/0. SHOW 3/0 PER TABLE NEC 250.66. ALSO
 CORRECT NOTE 6 TO SHOW 3/0.
 11. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO THE
 ELECTRICAL SCOPE OF WORK.
 12. PROVIDE GENERAL NOTES TO SHEET E2.1 TO MAINTAIN
 REQUIRED DEPTH PER NEC 300.5 FOR ALL U/G CONDUIT.
 13. PLEASE CLARIFY THE NON-REQUIRED COPS NOTES PROVIDED
 AS TO AHJ AUTHORIZATION TO EXCLUDE THE REQUIREMENTS OF
 NEC 708 TO THIS PROJECT.
 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  