2016-06-13 11:57:10 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16071078 |
| ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| CONT: HEDRICK BROTHERS |
| TEL: 561-662-8049 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: FRI. JUNE 10/ 2016 |
| ACTION: DENIED |
| |
| 1) MISSING DOCUMENTS 2014 FLORIDA BUILDING CODE W 2014 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| |
| 1A) SOILS REPORT: 2014 FBC-B 1803.5.2 QUESTIONABLE |
| SOIL. WHERE THE CLASSIFICATION, STRENGTH OR |
| COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 1B) ENERGY CALCULATIONS: 2014 FBC-ENERGY CODE. C401.2 |
| APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE |
| OF THE FOLLOWING: |
| 1B)(1.) THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| |
| 1B)(2.) THE REQUIREMENTS OF SECTIONS C402, C403, C404 |
| AND C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL |
| COMPLY WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| |
| 1B)(3.) THE REQUIREMENTS OF SECTION C407, C402.4, |
| C403.2, C404, C405.2, C405.3, C405.4, C405.6 AND |
| C405.7. THE BUILDING ENERGY COST SHALL BE EQUAL TO OR |
| LESS THAN 85 PERCENT OF THE STANDARD REFERENCE DESIGN |
| BUILDING. |
| |
| 2) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR |
| PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 |
| POUNDS PER SQUARE INCH |
| 4. FOR PILE DRIVING |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION |
| STEEL WELDED FRAMEWORK (BAR JOIST & ROOF DECK). |
| |
| 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. |
| |
| 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. |
| |
| 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 3) SHEET LS-100 & LS-101: |
| |
| 3A) DEPICTED ON SHEET LS-100 DEPICTS THE FLOOR PLAN FOR |
| THE 1ST & 2ND FLOOR. SHEET LS-101 LIST THERE ARE ONLY 2 |
| OCCUPANCIES FOR THIS BUILDING, A R2 AND A S2 / ENCLOSED |
| PARKING GARAGE. THERE ARE ACTUALLY (4) TYPES OF |
| OCCUPANCIES IN THIS STRUCTURE, ASSEMBLY USAGE, |
| BUSINESS, R2 DORMITORIES & S2 ENCLOSED PARKING GARAGE. |
| PLEASE REFER TO THE 2012 IBC-B BASE CODE FOR THE 5TH |
| EDITION OF THE FLORIDA BUILDING CODE- BUILDING. SECTION |
| 304.1 BUSINESS OCCUPANCY UNDER THE CODE COMMENTARY. |
| FIRE STATIONS WILL BE A MIX OF OFFICES, PARKING AND |
| MAINTENANCE FACILITIES, FOR THE FIRE ENGINES AND LIVING |
| SPACES FOR THE FIRE FIGHTERS. OFTEN A MEETING ROOM THAT |
| IS OPEN TO THE PUBLIC IS ALSO INCLUDED. THIS TYPE OF |
| FACILITY IS A MIX OF A, B, R & S OCCUPANCIES. |
| |
| 3B) THE 1ST FLOOR APPEARS TO BE A BUSINESS USE |
| OCCUPANCY, THE 2ND FLOOR IS A MIXED USE OCCUPANCY, WHEN |
| THE OCCUPANCY USAGE IS OVER 10% OF THE FLOOR AREA IT IS |
| NO LONGER AN INCIDENTAL USE AREA SEE FBC-B 509.3. THE |
| DORMS HAVE 600 SQ. FT. /50= 12 OCCUPANTS, AN A3 GYM |
| USAGE OF 696 SQ. FT./ 50= 14 OCCUPANTS. THE STORAGE |
| CLOSETS TOTAL 102 SQ. FT. AND LAUNDRY ARE ANCILLARY USE |
| TO THE MAIN OCCUPANCY. |
| |
| 3C) THE ISSUE WITH THE 2ND FLOOR EVEN IF YOU CONSIDER |
| THE WHOLE FLOOR THE R2 OCCUPANCY YOU STILL HAVE TO RATE |
| THE DORM ROOMS IN ACCORDANCE WITH 2014 FBC-B 420.2. SEE |
| SLEEPING UNITS STILL NEED TO HAVE FIRE PARTITIONS IN |
| ACCORDANCE WITH 708 AND OPENING PROTECTIVES IN |
| ACCORDANCE WITH TABLE 716.5. COMPLIANCE WITH FBC-B |
| 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS WILL NEED |
| TO BE COMPLIED WITH. |
| |
| 3D) EVEN THOUGH THIS BEING A IIIB TYPE STRUCTURE TABLE |
| 601 DOESN?T REQUIRE FIRE RATING PLEASE REFER TO FBC-B |
| 420.3 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES |
| SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR |
| ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR |
| SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. |
| |
| 3E) IN REGARDS TO THE 2ND FLOOR CORRIDOR AND OCCUPANT |
| LOAD OF THE DORMITORY?S. THE DORMS HAVING A SQUARE |
| FOOTAGE OF 600 SQ. FEET/ 50= 12 OCCUPANTS. IN THE 2014 |
| FBC-B TABLE 1018.1 WHEN THE OCCUPANT LOAD IS GREATER |
| THAN 10 THERE IS STILL A ? HOUR FIRE RATING REQUIRED |
| AND OPENING PROTECTIVES. I?VE SPOKEN TO THE BUILDING |
| OFFICIAL ROBERT BROWN ABOUT THIS ISSUE. IN HOW THE |
| DORMITORY?S ARE GOING TO BE USED HE BELIEVES THE DORMS |
| WILL BE SINGLE USER SLEEPING ROOMS OR THERE WILL NEVER |
| BE MORE THAN A TOTAL OF 7 SLEEPING AT THE SAME TIME. |
| THE BUILDING OFFICIAL WOULD LIKE A LETTER FROM THE FIRE |
| DEPARTMENT DECLARING THE USAGE AS SUCH AND THIS LETTER |
| WILL THEN BE MADE AS PART OF THE PERMIT PACKAGE. |
| |
| 3F) SHEET LS100. THE 2ND FLOOR THE EAST END OF CORRIDOR |
| 37 WHERE IT LEADS TO THE FIRE POLE THERE IS A DOOR |
| MISSING IN THE 2 HOUR FIRE RATED WALL SEPARATING THE S2 |
| AND R2 OCCUPANCIES. SEE TABLE 716.5. SHEET A-102 DOES |
| SHOW THE MISSING DOOR. |
| |
| 3G) SHEET LS100 SHOWS A LIFT ROOM # 19. PLEASE CLARIFY |
| IF YOU ARE DEFINING THIS UNIT AS A PLATFORM LIFT |
| COVERED UNDER THE 2014 FBC-ACCESSIBILITY CODE 206.7 AND |
| COMPLYING WITH THE REQUIREMENTS OF 410, OR LULA?S |
| LIMITED USE/ LIMITED APPLICATION ELEVATORS THAT COMPLY |
| WITH SECTION 408 AND ASME A17.1? |
| PLEASE NOTE PLATFORM LIFTS ARE LIMITED IN NEW |
| CONSTRUCTION SEE COMPLIANCE WHERE THEY CAN BE |
| INSTALLED. |
| PLEASE PROVIDE THE MANUFACTURERS SHOP DRAWING FOR |
| INSTALLATION. |
| |
| 4) SHEET LS-200: |
| 4A) PLEASE PROVIDE THE AREA CONCRETE BLOCK MANUFACTURER |
| THAT WILL BE PROVIDING THE 2 HOUR FIRE RATED BLOCK, IN |
| THE EQUIVALENT THICKNESS PER 2014 FBC-B TABLE 722.3.2. |
| |
| 4B) THE LS-200 DOES NOT PROVIDE ANY FLOOR FIRE |
| ASSEMBLIES. WITH THE 1ST FLOOR BEING A BUSINESS |
| OCCUPANCY AND THE 2ND FLOOR HAVING A MIXED OCCUPANCY |
| COMPLIANCE WITH 508.4.4 OCCUPANCY SEPARATION AND |
| 508.4.4.1 CONSTRUCTION. TABLE 707.3.10 FIRE-RESISTANCE |
| RATING REQUIREMENTS FOR FIRE BARRIER ASSEMBLIES OR |
| HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS: B / A3 & R2 |
| REQUIRE 2HOURS. |
| REQUIRED SEPARATIONS SHALL BE FIRE BARRIERS CONSTRUCTED |
| IN ACCORDANCE WITH HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| ACCORDANCE WITH SECTION 711. |
| 714.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. PENETRATIONS |
| OF THE FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING |
| ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING |
| ASSEMBLY SHALL COMPLY WITH SECTIONS 714.4.1.1 THROUGH |
| 714.4.1.3. |
| |
| 5) NOTICE ONLY!!! THE ARCHITECTURAL AND STRUCTURAL |
| SHEETS DOES NOT PROVIDE AT WHAT ELEVATION THE FINISH |
| FLOOR ELEVATION WILL BE. THE OLD FIRE STATION THAT IS |
| TO BE DEMOLISHED FINISH FLOOR IS AT AN ELEVATION OF |
| 16.24 NGVD. HABITABLE AREAS/ TRUCK BAYS 15.93 NGVD. THE |
| NEW PROPOSED ELEVATION FOR THE FINISH FLOOR IS AN |
| ELEVATION OF 15.53 NGVD OR APPROXIMATELY 9 INCH LOWER. |
| OUR CURRENT FLOOD MAPS SHOW A FLOOD ZONE SHOW THE FLOOD |
| ZONE A9 AT A ELEVATION 13.0 NGVD JUST WEST OF PARKER |
| AND PARK PLACE. THE NEW PROPOSED FLOOD MAPS SHOW THE A9 |
| FLOOD ZONE ENCROACHING FURTHER EAST ON PARK PLACE. THE |
| NEW PROPOSED FLOOD MAP ALSO DROPPED THE ELEVATION OF |
| THE A9 FLOOD ZONE TO AN ELEVATION OF 12.7 FT. NGVD. |
| ASCE 24-05 FOR ESSENTIAL FACILITIES TABLE 1-1 FIRE |
| STATIONS A BUILDING CATEGORY IV. TABLE 2-1 FOR CATEGORY |
| IV STRUCTURES REQUIRES A ELEVATION OF BFE(BASE FLOOD |
| ELEVATION)+ 2 FT. THE PROPOSED NEW BASE FLOOD ELEVATION |
| OF 12.7 FT. + 2.0 FT= 14.7 FT. NGVD AS THE MINIMUM |
| BUILDING HEIGHT. THE NEW PROPOSED SLAB HEIGHT OF 15.53 |
| FT. NGVD IS CODE COMPLIANT TO THE MORE STRINGENT ASCE |
| 24-5. |
| |
| 6A) SHEET A-100 ON THE 1ST FLOOR THE DOOR SWING IS NOT |
| TURNED ON THE EXTERIOR DOORS 01,22,23 & 23A. ADDITIONAL |
| INFORMATION REQUIRED. 107.2.1.3. |
| |
| 6B) THE DORM WALLS AND DOORS DO NOT SHOW COMPLIANCE |
| WITH: WITH 2014 FBC-B 420.2. SEE SLEEPING UNITS STILL |
| NEED TO HAVE FIRE PARTITIONS IN ACCORDANCE WITH 708 AND |
| OPENING PROTECTIVES IN ACCORDANCE WITH TABLE 716.5. |
| |
| 7A) SHEET A-100A THE MAIN ENTRY STAIR ONLY SHOWS ONE |
| HANDRAIL PLEASE SHOW COMPLIANCE WITH 2014 FBC-B |
| 1009.15 HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON |
| EACH SIDE AND SHALL COMPLY WITH SECTION 1012. |
| NOTE SHEET C-5.01 SHOWS AN ELEVATION CHANGE OF 26 ? |
| INCHES GUARDRAILS NOT REQUIRED. SHEET A-100 MISSING THE |
| KNEE WALLS FOR THE RAMP FRONT ENTRY COURTYARD AND KNEE |
| WALL BETWEEN THE FRONT ENTRY COURTYARD AND DRIVE AISLE. |
| |
| 7B) SHEET A-100A THE STAIR # 1 EXTERIOR LANDING AS |
| SHOWN ON THIS SHEET IS NOT CONSISTENT WITH THE DESIGN |
| SHOWN ON SHEET A-100A. THE LANDING AND STAIR ARE |
| NARROWER ON SHEET A-100A AS WELL AS THERE IS A 42 INCH |
| HIGH KNEE WALL ON SHEET A-100A. ONLY 1 HANDRAIL IS |
| SHOWN ON SHEET A-100A. COMPLY WITH 2014 FBC-B |
| 1009.15 HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON |
| EACH SIDE AND SHALL COMPLY WITH SECTION 1012. |
| |
| 8) SHEET C-5.01 SHOWS AN ACCESSIBLE PARKING ON THE SIDE |
| STREET PARK PLACE. SHEET C-5.01 SHOW THE USE OF (2) |
| FDOT TYPE CR-E ADA RAMPS WITH WHAT APPEARS TO BE A |
| RAISED CONCRETE WALKWAY BETWEEN AND THE LOCATION OF THE |
| HANDICAPPED PARKING SIGN CENTERED IN THIS AREA. THE ARE |
| 2 ISSUES WITH THIS AREA: |
| |
| 8A) COMPLIANCE WITH 2014 FBC-ACCESS. CODE 502.2.1 |
| ON-STREET PARALLEL PARKING. |
| SPACES MUST COMPLY WITH SECTIONS 208 AND 502 OF THE ADA |
| STANDARDS FOR ACCESSIBLE DESIGN. CURBS ADJACENT TO SUCH |
| SPACES MUST BE OF A HEIGHT THAT DOES NOT INTERFERE WITH |
| THE OPENING AND CLOSING OF MOTOR VEHICLE DOORS. IF |
| THERE IS A VAN THAT USES THIS ACCESSIBLE PARKING PLACE |
| & THE VAN USES A SIDE DOOR LIFT THERE APPEARS THERE |
| WOULD POSSIBLY BE VARIATIONS IN HEIGHT OF THE CURB |
| MAKING THE LIFT USELESS. |
| |
| 8B) THE OTHER ISSUE IS THE POSITIONING OF THE |
| ACCESSIBLE PARKING SPACE SIGN. AGAIN USING THE EXAMPLE |
| OF AN ACCESSIBLE VAN WITH A SIDE DOOR WHEEL CHAIR LIFT |
| THE LOCATION OF THE PROPOSED SIGN WOULDN?T ALLOW THE |
| LIFT TO FULL EXTEND ALLOWING THE OCCUPANT TO HAVE |
| ACCESS TO THE PUBLIC BUILDING. CODE 502.2.1 ON-STREET |
| PARALLEL PARKING. 208.2.5.1. |
| |
| 9) SHEET A-101A DETAIL C/A301 SHOWS A DETAIL THAT CUTS |
| THROUGH BOTH STAIRWELL 1 & 2. THIS DETAIL DOES NOT SHOW |
| HOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE SECTION |
| 307.4 VERTICAL CLEARANCE AND FIGURE 307.4. |
| |
| 10) SHEET A-102A INDICATES A FIRE RATED CHASE FOR THE |
| RANGE EXHAUST DUCT, THE DETAIL IS FOR SHALT WALL |
| CONSTRUCTION, PLEASE PROVIDE A DETAIL HOW THE BOTTOM OF |
| THE SHAFT WILL BE SEALED OR PENETRATION THROUGH THE |
| RATED FLOOR. 713.11 ENCLOSURE AT THE BOTTOM. |
| SHAFTS THAT DO NOT EXTEND TO THE BOTTOM OF THE BUILDING |
| OR STRUCTURE SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| |
| 1. THEY SHALL BE ENCLOSED AT THE LOWEST LEVEL WITH |
| CONSTRUCTION OF THE SAME FIRE-RESISTANCE RATING AS THE |
| LOWEST FLOOR THROUGH WHICH THE SHAFT PASSES, BUT NOT |
| LESS THAN THE RATING REQUIRED FOR THE SHAFT ENCLOSURE. |
| |
| 2. THEY SHALL TERMINATE IN A ROOM HAVING A USE RELATED |
| TO THE PURPOSE OF THE SHAFT. THE ROOM SHALL BE |
| SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE |
| BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 711, OR BOTH. THE FIRE-RESISTANCE RATING AND |
| OPENING PROTECTIVES SHALL BE AT LEAST EQUAL TO THE |
| PROTECTION REQUIRED FOR THE SHAFT ENCLOSURE. |
| |
| 3. THEY SHALL BE PROTECTED BY APPROVED FIRE DAMPERS |
| INSTALLED IN ACCORDANCE WITH THEIR LISTING AT THE |
| LOWEST FLOOR LEVEL WITHIN THE SHAFT ENCLOSURE. |
| |
| FLOOR ASSEMBLIES. 714.4.1.1 THROUGH PENETRATIONS. |
| THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED |
| HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION |
| 714.4.1.1.1 OR 714.4.1.1.2. |
| |
| 11) SHEET A104-B SHOWS THE USE OF ICYNENE INSULATION |
| THERMO-BARRIER AND VAPOR RETARDER SPRAY PLEASE PROVIDE |
| THE MANUFACTURERS TESTING REPORT ICC-ES REPORT ESR-1826 |
| OR NEWER. THERE ARE VARIOUS SUB-SYSTEMS WITHIN THIS |
| REPORT, IDENTIFY WHICH INSTALLATION WILL IS APPLIED. |
| SHOW COMPLIANCE WITH 2603.4.1.6 PROTECTION AGAINST |
| IGNITION AS WELL. PLANS INDICATE A R-19 THICKNESS OF |
| ICYNENE. |
| |
| 12) SHEET A-200 & A-201 SHOW WINDOW AND DOOR PRESSURES. |
| THERE IS NO WIND DESIGN CRITERIA FOR THESE PRESSURES. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE. |
| ARE THEY IN VULT OR VASD, PROVIDE THE MEAN ROOF HEIGHT. |
| 12.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND |
| SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 12.2. RISK CATEGORY. |
| |
| 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 13) MISSING PRODUCT APPROVALS: 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| (B) WINDOWS - FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH |
| OPENING SIZE. |
| |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 14) SHEET A300 SHOWS ROOF TOP EQUIPMENT REFERS TO |
| A-502, THIS SHEET ONLY DETAILS THE ROOF TOP MECHANICAL |
| SCREEN. THERE ARE DETAILS FOUND ON S-302 DETAIL 2 & 3 |
| NOT ALL WELDS ARE DIMENSIONED AS TO THEIR SIZE. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NO |
| PRODUCT APPROVALS WERE SUBMITTED FOR THE LOUVER |
| ELEMENT. |
| |
| 15) SHEET S-102 SHOWS A GENERIC ROOF TOP DETAIL FOR |
| ROOF TOP FRAMING AROUND ROOF TOP OPENINGS. TO DATE |
| THERE HAS BEEN NO ROOF TOP CURBS FOR EITHER RTU?S OR |
| INTAKE OR EXHAUST FANS SUBMITTED. PLEASE PROVIDE |
| DOCUMENTATION FOR ATTACHMENT OF THE CURB TO THE ROOF |
| TOP FRAMING AS WELL AS THE ATTACHMENT OF THE RTU OR |
| ROOF TOP FAN TO ITS BASE. SHOW COMPLIANCE WITH 2014 |
| FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM |
| MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| WIND LOADS? |
| |
| 16A) SHEETS A-403A & A-405 BOTH SHOW THE HANDRAIL |
| STARTING A HORIZONTAL EXTENSION AT THE FIRST RISER |
| CAUSING THE EXTENSION TO BE AT 3 FT. 6 INCHES. NOTE IN |
| THE FBC-B SECTION 1012.6 THE HANDRAIL SHALL CONTINUE |
| ITS SLOPE PAST THE 1ST RISE THE DISTANCE OF THE TREAD |
| BEFORE THE 12 INCH HORIZONTAL EXTENSION STARTS. THE |
| HANDRAIL DEPICTED AT THE TOP OF THE STAIR AT 3 FEET |
| ABOVE THE FINISH FLOOR WILL END UP AT 3 FOOT ABOVE THE |
| FINISH FLOOR NOT THE 3 FOOT- 6 INCHES AS SHOWN. |
| |
| 16B) THE DETAILS ON THESE SHEETS INDICATES THE STAIRS |
| ARE TO BE PRE-ENGINEERED AND MANUFACTURED AND WITH |
| CONCRETE STEEL PAN TREADS. THERE IS NO MENTION OF THE |
| RISERS BEING SOLID. 1009.7.5.3 SOLID RISERS. |
| |
| 16C) SHEETS A-403A & A-405 NEITHER OF THESE SHEETS |
| PROVIDE A GUARDRAIL DETAIL , SHOW COMPLIANCE WITH: |
| |
| 1013.3 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS THAN |
| 42 INCHES (1067 MM) HIGH, MEASURED VERTICALLY AS |
| FOLLOWS: |
| 2. ON STAIRS, FROM THE LINE CONNECTING THE LEADING |
| EDGES OF THE TREAD NOSINGS; |
| |
| 1013.4 OPENING LIMITATIONS. REQUIRED GUARDS SHALL NOT |
| HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE 4 INCHES |
| (102 MM) IN DIAMETER FROM THE WALKING SURFACE TO THE |
| REQUIRED GUARD HEIGHT. EXCEPTIONS: |
| |
| 1. FROM A HEIGHT OF 36 INCHES (914 MM) TO 42 INCHES |
| (1067 MM), GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW |
| PASSAGE OF A SPHERE 43/8 INCHES (111 MM) IN DIAMETER. |
| |
| 2. THE TRIANGULAR OPENINGS AT THE OPEN SIDES OF A |
| STAIR, FORMED BY THE RISER, TREAD AND BOTTOM RAIL SHALL |
| NOT ALLOW PASSAGE OF A SPHERE 6 INCHES (152 MM) IN |
| DIAMETER. |
| |
| 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |