Plan Review Notes
Plan Review Notes For Permit 16051078
Permit Number 16051078
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-13 11:57:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071078
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. JUNE 10/ 2016
 ACTION: DENIED
  
 1) MISSING DOCUMENTS 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION:
 107.3.5.1 COMMERCIAL BUILDINGS:
  
 1A) SOILS REPORT: 2014 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 1B) ENERGY CALCULATIONS: 2014 FBC-ENERGY CODE. C401.2
 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE
 OF THE FOLLOWING:
 1B)(1.) THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
  
 1B)(2.) THE REQUIREMENTS OF SECTIONS C402, C403, C404
 AND C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL
 COMPLY WITH EITHER SECTION C406.2, C406.3 OR C406.4.
  
 1B)(3.) THE REQUIREMENTS OF SECTION C407, C402.4,
 C403.2, C404, C405.2, C405.3, C405.4, C405.6 AND
 C405.7. THE BUILDING ENERGY COST SHALL BE EQUAL TO OR
 LESS THAN 85 PERCENT OF THE STANDARD REFERENCE DESIGN
 BUILDING.
  
 2) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR
 PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
 STEEL WELDED FRAMEWORK (BAR JOIST & ROOF DECK).
  
 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED.
  
 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) SHEET LS-100 & LS-101:
  
 3A) DEPICTED ON SHEET LS-100 DEPICTS THE FLOOR PLAN FOR
 THE 1ST & 2ND FLOOR. SHEET LS-101 LIST THERE ARE ONLY 2
 OCCUPANCIES FOR THIS BUILDING, A R2 AND A S2 / ENCLOSED
 PARKING GARAGE. THERE ARE ACTUALLY (4) TYPES OF
 OCCUPANCIES IN THIS STRUCTURE, ASSEMBLY USAGE,
 BUSINESS, R2 DORMITORIES & S2 ENCLOSED PARKING GARAGE.
 PLEASE REFER TO THE 2012 IBC-B BASE CODE FOR THE 5TH
 EDITION OF THE FLORIDA BUILDING CODE- BUILDING. SECTION
 304.1 BUSINESS OCCUPANCY UNDER THE CODE COMMENTARY.
 FIRE STATIONS WILL BE A MIX OF OFFICES, PARKING AND
 MAINTENANCE FACILITIES, FOR THE FIRE ENGINES AND LIVING
 SPACES FOR THE FIRE FIGHTERS. OFTEN A MEETING ROOM THAT
 IS OPEN TO THE PUBLIC IS ALSO INCLUDED. THIS TYPE OF
 FACILITY IS A MIX OF A, B, R & S OCCUPANCIES.
  
 3B) THE 1ST FLOOR APPEARS TO BE A BUSINESS USE
 OCCUPANCY, THE 2ND FLOOR IS A MIXED USE OCCUPANCY, WHEN
 THE OCCUPANCY USAGE IS OVER 10% OF THE FLOOR AREA IT IS
 NO LONGER AN INCIDENTAL USE AREA SEE FBC-B 509.3. THE
 DORMS HAVE 600 SQ. FT. /50= 12 OCCUPANTS, AN A3 GYM
 USAGE OF 696 SQ. FT./ 50= 14 OCCUPANTS. THE STORAGE
 CLOSETS TOTAL 102 SQ. FT. AND LAUNDRY ARE ANCILLARY USE
 TO THE MAIN OCCUPANCY.
  
 3C) THE ISSUE WITH THE 2ND FLOOR EVEN IF YOU CONSIDER
 THE WHOLE FLOOR THE R2 OCCUPANCY YOU STILL HAVE TO RATE
 THE DORM ROOMS IN ACCORDANCE WITH 2014 FBC-B 420.2. SEE
 SLEEPING UNITS STILL NEED TO HAVE FIRE PARTITIONS IN
 ACCORDANCE WITH 708 AND OPENING PROTECTIVES IN
 ACCORDANCE WITH TABLE 716.5. COMPLIANCE WITH FBC-B
 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS WILL NEED
 TO BE COMPLIED WITH.
  
 3D) EVEN THOUGH THIS BEING A IIIB TYPE STRUCTURE TABLE
 601 DOESN?T REQUIRE FIRE RATING PLEASE REFER TO FBC-B
 420.3 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3E) IN REGARDS TO THE 2ND FLOOR CORRIDOR AND OCCUPANT
 LOAD OF THE DORMITORY?S. THE DORMS HAVING A SQUARE
 FOOTAGE OF 600 SQ. FEET/ 50= 12 OCCUPANTS. IN THE 2014
 FBC-B TABLE 1018.1 WHEN THE OCCUPANT LOAD IS GREATER
 THAN 10 THERE IS STILL A ? HOUR FIRE RATING REQUIRED
 AND OPENING PROTECTIVES. I?VE SPOKEN TO THE BUILDING
 OFFICIAL ROBERT BROWN ABOUT THIS ISSUE. IN HOW THE
 DORMITORY?S ARE GOING TO BE USED HE BELIEVES THE DORMS
 WILL BE SINGLE USER SLEEPING ROOMS OR THERE WILL NEVER
 BE MORE THAN A TOTAL OF 7 SLEEPING AT THE SAME TIME.
 THE BUILDING OFFICIAL WOULD LIKE A LETTER FROM THE FIRE
 DEPARTMENT DECLARING THE USAGE AS SUCH AND THIS LETTER
 WILL THEN BE MADE AS PART OF THE PERMIT PACKAGE.
  
 3F) SHEET LS100. THE 2ND FLOOR THE EAST END OF CORRIDOR
 37 WHERE IT LEADS TO THE FIRE POLE THERE IS A DOOR
 MISSING IN THE 2 HOUR FIRE RATED WALL SEPARATING THE S2
 AND R2 OCCUPANCIES. SEE TABLE 716.5. SHEET A-102 DOES
 SHOW THE MISSING DOOR.
  
 3G) SHEET LS100 SHOWS A LIFT ROOM # 19. PLEASE CLARIFY
 IF YOU ARE DEFINING THIS UNIT AS A PLATFORM LIFT
 COVERED UNDER THE 2014 FBC-ACCESSIBILITY CODE 206.7 AND
 COMPLYING WITH THE REQUIREMENTS OF 410, OR LULA?S
 LIMITED USE/ LIMITED APPLICATION ELEVATORS THAT COMPLY
 WITH SECTION 408 AND ASME A17.1?
 PLEASE NOTE PLATFORM LIFTS ARE LIMITED IN NEW
 CONSTRUCTION SEE COMPLIANCE WHERE THEY CAN BE
 INSTALLED.
 PLEASE PROVIDE THE MANUFACTURERS SHOP DRAWING FOR
 INSTALLATION.
  
 4) SHEET LS-200:
 4A) PLEASE PROVIDE THE AREA CONCRETE BLOCK MANUFACTURER
 THAT WILL BE PROVIDING THE 2 HOUR FIRE RATED BLOCK, IN
 THE EQUIVALENT THICKNESS PER 2014 FBC-B TABLE 722.3.2.
  
 4B) THE LS-200 DOES NOT PROVIDE ANY FLOOR FIRE
 ASSEMBLIES. WITH THE 1ST FLOOR BEING A BUSINESS
 OCCUPANCY AND THE 2ND FLOOR HAVING A MIXED OCCUPANCY
 COMPLIANCE WITH 508.4.4 OCCUPANCY SEPARATION AND
 508.4.4.1 CONSTRUCTION. TABLE 707.3.10 FIRE-RESISTANCE
 RATING REQUIREMENTS FOR FIRE BARRIER ASSEMBLIES OR
 HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS: B / A3 & R2
 REQUIRE 2HOURS.
 REQUIRED SEPARATIONS SHALL BE FIRE BARRIERS CONSTRUCTED
 IN ACCORDANCE WITH HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711.
 714.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. PENETRATIONS
 OF THE FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING
 ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY SHALL COMPLY WITH SECTIONS 714.4.1.1 THROUGH
 714.4.1.3.
  
 5) NOTICE ONLY!!! THE ARCHITECTURAL AND STRUCTURAL
 SHEETS DOES NOT PROVIDE AT WHAT ELEVATION THE FINISH
 FLOOR ELEVATION WILL BE. THE OLD FIRE STATION THAT IS
 TO BE DEMOLISHED FINISH FLOOR IS AT AN ELEVATION OF
 16.24 NGVD. HABITABLE AREAS/ TRUCK BAYS 15.93 NGVD. THE
 NEW PROPOSED ELEVATION FOR THE FINISH FLOOR IS AN
 ELEVATION OF 15.53 NGVD OR APPROXIMATELY 9 INCH LOWER.
 OUR CURRENT FLOOD MAPS SHOW A FLOOD ZONE SHOW THE FLOOD
 ZONE A9 AT A ELEVATION 13.0 NGVD JUST WEST OF PARKER
 AND PARK PLACE. THE NEW PROPOSED FLOOD MAPS SHOW THE A9
 FLOOD ZONE ENCROACHING FURTHER EAST ON PARK PLACE. THE
 NEW PROPOSED FLOOD MAP ALSO DROPPED THE ELEVATION OF
 THE A9 FLOOD ZONE TO AN ELEVATION OF 12.7 FT. NGVD.
 ASCE 24-05 FOR ESSENTIAL FACILITIES TABLE 1-1 FIRE
 STATIONS A BUILDING CATEGORY IV. TABLE 2-1 FOR CATEGORY
 IV STRUCTURES REQUIRES A ELEVATION OF BFE(BASE FLOOD
 ELEVATION)+ 2 FT. THE PROPOSED NEW BASE FLOOD ELEVATION
 OF 12.7 FT. + 2.0 FT= 14.7 FT. NGVD AS THE MINIMUM
 BUILDING HEIGHT. THE NEW PROPOSED SLAB HEIGHT OF 15.53
 FT. NGVD IS CODE COMPLIANT TO THE MORE STRINGENT ASCE
 24-5.
  
 6A) SHEET A-100 ON THE 1ST FLOOR THE DOOR SWING IS NOT
 TURNED ON THE EXTERIOR DOORS 01,22,23 & 23A. ADDITIONAL
 INFORMATION REQUIRED. 107.2.1.3.
  
 6B) THE DORM WALLS AND DOORS DO NOT SHOW COMPLIANCE
 WITH: WITH 2014 FBC-B 420.2. SEE SLEEPING UNITS STILL
 NEED TO HAVE FIRE PARTITIONS IN ACCORDANCE WITH 708 AND
 OPENING PROTECTIVES IN ACCORDANCE WITH TABLE 716.5.
  
 7A) SHEET A-100A THE MAIN ENTRY STAIR ONLY SHOWS ONE
 HANDRAIL PLEASE SHOW COMPLIANCE WITH 2014 FBC-B
 1009.15 HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE AND SHALL COMPLY WITH SECTION 1012.
 NOTE SHEET C-5.01 SHOWS AN ELEVATION CHANGE OF 26 ?
 INCHES GUARDRAILS NOT REQUIRED. SHEET A-100 MISSING THE
 KNEE WALLS FOR THE RAMP FRONT ENTRY COURTYARD AND KNEE
 WALL BETWEEN THE FRONT ENTRY COURTYARD AND DRIVE AISLE.
  
 7B) SHEET A-100A THE STAIR # 1 EXTERIOR LANDING AS
 SHOWN ON THIS SHEET IS NOT CONSISTENT WITH THE DESIGN
 SHOWN ON SHEET A-100A. THE LANDING AND STAIR ARE
 NARROWER ON SHEET A-100A AS WELL AS THERE IS A 42 INCH
 HIGH KNEE WALL ON SHEET A-100A. ONLY 1 HANDRAIL IS
 SHOWN ON SHEET A-100A. COMPLY WITH 2014 FBC-B
 1009.15 HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE AND SHALL COMPLY WITH SECTION 1012.
  
 8) SHEET C-5.01 SHOWS AN ACCESSIBLE PARKING ON THE SIDE
 STREET PARK PLACE. SHEET C-5.01 SHOW THE USE OF (2)
 FDOT TYPE CR-E ADA RAMPS WITH WHAT APPEARS TO BE A
 RAISED CONCRETE WALKWAY BETWEEN AND THE LOCATION OF THE
 HANDICAPPED PARKING SIGN CENTERED IN THIS AREA. THE ARE
 2 ISSUES WITH THIS AREA:
  
 8A) COMPLIANCE WITH 2014 FBC-ACCESS. CODE 502.2.1
 ON-STREET PARALLEL PARKING.
 SPACES MUST COMPLY WITH SECTIONS 208 AND 502 OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN. CURBS ADJACENT TO SUCH
 SPACES MUST BE OF A HEIGHT THAT DOES NOT INTERFERE WITH
 THE OPENING AND CLOSING OF MOTOR VEHICLE DOORS. IF
 THERE IS A VAN THAT USES THIS ACCESSIBLE PARKING PLACE
 & THE VAN USES A SIDE DOOR LIFT THERE APPEARS THERE
 WOULD POSSIBLY BE VARIATIONS IN HEIGHT OF THE CURB
 MAKING THE LIFT USELESS.
  
 8B) THE OTHER ISSUE IS THE POSITIONING OF THE
 ACCESSIBLE PARKING SPACE SIGN. AGAIN USING THE EXAMPLE
 OF AN ACCESSIBLE VAN WITH A SIDE DOOR WHEEL CHAIR LIFT
 THE LOCATION OF THE PROPOSED SIGN WOULDN?T ALLOW THE
 LIFT TO FULL EXTEND ALLOWING THE OCCUPANT TO HAVE
 ACCESS TO THE PUBLIC BUILDING. CODE 502.2.1 ON-STREET
 PARALLEL PARKING. 208.2.5.1.
  
 9) SHEET A-101A DETAIL C/A301 SHOWS A DETAIL THAT CUTS
 THROUGH BOTH STAIRWELL 1 & 2. THIS DETAIL DOES NOT SHOW
 HOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE SECTION
 307.4 VERTICAL CLEARANCE AND FIGURE 307.4.
  
 10) SHEET A-102A INDICATES A FIRE RATED CHASE FOR THE
 RANGE EXHAUST DUCT, THE DETAIL IS FOR SHALT WALL
 CONSTRUCTION, PLEASE PROVIDE A DETAIL HOW THE BOTTOM OF
 THE SHAFT WILL BE SEALED OR PENETRATION THROUGH THE
 RATED FLOOR. 713.11 ENCLOSURE AT THE BOTTOM.
 SHAFTS THAT DO NOT EXTEND TO THE BOTTOM OF THE BUILDING
 OR STRUCTURE SHALL COMPLY WITH ONE OF THE FOLLOWING:
  
 1. THEY SHALL BE ENCLOSED AT THE LOWEST LEVEL WITH
 CONSTRUCTION OF THE SAME FIRE-RESISTANCE RATING AS THE
 LOWEST FLOOR THROUGH WHICH THE SHAFT PASSES, BUT NOT
 LESS THAN THE RATING REQUIRED FOR THE SHAFT ENCLOSURE.
  
 2. THEY SHALL TERMINATE IN A ROOM HAVING A USE RELATED
 TO THE PURPOSE OF THE SHAFT. THE ROOM SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. THE FIRE-RESISTANCE RATING AND
 OPENING PROTECTIVES SHALL BE AT LEAST EQUAL TO THE
 PROTECTION REQUIRED FOR THE SHAFT ENCLOSURE.
  
 3. THEY SHALL BE PROTECTED BY APPROVED FIRE DAMPERS
 INSTALLED IN ACCORDANCE WITH THEIR LISTING AT THE
 LOWEST FLOOR LEVEL WITHIN THE SHAFT ENCLOSURE.
  
 FLOOR ASSEMBLIES. 714.4.1.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 714.4.1.1.1 OR 714.4.1.1.2.
  
 11) SHEET A104-B SHOWS THE USE OF ICYNENE INSULATION
 THERMO-BARRIER AND VAPOR RETARDER SPRAY PLEASE PROVIDE
 THE MANUFACTURERS TESTING REPORT ICC-ES REPORT ESR-1826
 OR NEWER. THERE ARE VARIOUS SUB-SYSTEMS WITHIN THIS
 REPORT, IDENTIFY WHICH INSTALLATION WILL IS APPLIED.
 SHOW COMPLIANCE WITH 2603.4.1.6 PROTECTION AGAINST
 IGNITION AS WELL. PLANS INDICATE A R-19 THICKNESS OF
 ICYNENE.
  
 12) SHEET A-200 & A-201 SHOW WINDOW AND DOOR PRESSURES.
 THERE IS NO WIND DESIGN CRITERIA FOR THESE PRESSURES.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE.
 ARE THEY IN VULT OR VASD, PROVIDE THE MEAN ROOF HEIGHT.
 12.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 12.2. RISK CATEGORY.
  
 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 13) MISSING PRODUCT APPROVALS: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 (B) WINDOWS - FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE.
  
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 14) SHEET A300 SHOWS ROOF TOP EQUIPMENT REFERS TO
 A-502, THIS SHEET ONLY DETAILS THE ROOF TOP MECHANICAL
 SCREEN. THERE ARE DETAILS FOUND ON S-302 DETAIL 2 & 3
 NOT ALL WELDS ARE DIMENSIONED AS TO THEIR SIZE.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THE LOUVER
 ELEMENT.
  
 15) SHEET S-102 SHOWS A GENERIC ROOF TOP DETAIL FOR
 ROOF TOP FRAMING AROUND ROOF TOP OPENINGS. TO DATE
 THERE HAS BEEN NO ROOF TOP CURBS FOR EITHER RTU?S OR
 INTAKE OR EXHAUST FANS SUBMITTED. PLEASE PROVIDE
 DOCUMENTATION FOR ATTACHMENT OF THE CURB TO THE ROOF
 TOP FRAMING AS WELL AS THE ATTACHMENT OF THE RTU OR
 ROOF TOP FAN TO ITS BASE. SHOW COMPLIANCE WITH 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 16A) SHEETS A-403A & A-405 BOTH SHOW THE HANDRAIL
 STARTING A HORIZONTAL EXTENSION AT THE FIRST RISER
 CAUSING THE EXTENSION TO BE AT 3 FT. 6 INCHES. NOTE IN
 THE FBC-B SECTION 1012.6 THE HANDRAIL SHALL CONTINUE
 ITS SLOPE PAST THE 1ST RISE THE DISTANCE OF THE TREAD
 BEFORE THE 12 INCH HORIZONTAL EXTENSION STARTS. THE
 HANDRAIL DEPICTED AT THE TOP OF THE STAIR AT 3 FEET
 ABOVE THE FINISH FLOOR WILL END UP AT 3 FOOT ABOVE THE
 FINISH FLOOR NOT THE 3 FOOT- 6 INCHES AS SHOWN.
  
 16B) THE DETAILS ON THESE SHEETS INDICATES THE STAIRS
 ARE TO BE PRE-ENGINEERED AND MANUFACTURED AND WITH
 CONCRETE STEEL PAN TREADS. THERE IS NO MENTION OF THE
 RISERS BEING SOLID. 1009.7.5.3 SOLID RISERS.
  
 16C) SHEETS A-403A & A-405 NEITHER OF THESE SHEETS
 PROVIDE A GUARDRAIL DETAIL , SHOW COMPLIANCE WITH:
  
 1013.3 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS THAN
 42 INCHES (1067 MM) HIGH, MEASURED VERTICALLY AS
 FOLLOWS:
 2. ON STAIRS, FROM THE LINE CONNECTING THE LEADING
 EDGES OF THE TREAD NOSINGS;
  
 1013.4 OPENING LIMITATIONS. REQUIRED GUARDS SHALL NOT
 HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE 4 INCHES
 (102 MM) IN DIAMETER FROM THE WALKING SURFACE TO THE
 REQUIRED GUARD HEIGHT. EXCEPTIONS:
  
 1. FROM A HEIGHT OF 36 INCHES (914 MM) TO 42 INCHES
 (1067 MM), GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 43/8 INCHES (111 MM) IN DIAMETER.
  
 2. THE TRIANGULAR OPENINGS AT THE OPEN SIDES OF A
 STAIR, FORMED BY THE RISER, TREAD AND BOTTOM RAIL SHALL
 NOT ALLOW PASSAGE OF A SPHERE 6 INCHES (152 MM) IN
 DIAMETER.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  