2016-06-01 11:49:381ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050998
 6/1/2016
  
 1) SHEETS M202A, 203A, 204A, 205A, & 304A: PLEASE
 CLARIFY HOW O/A IS BEING SUPPLIED TO THE RESIDENTIAL
 UNITS, AND PROVIDE VENTILATION CALCULATIONS PER TABLE
 403.3.
 2) SHEET M201A: THE 1-WAY SUPPLY DIFFUSER IN THE POOL
 ACCESS ROOM 135A HAS A LABEL INDICATING -200 RETURN
 CFMS.
 3) REVISE THE EQUIPMENT SCHEDULES FOR THE KITCHEN
 SUPPLY FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER