2017-03-09 16:14:06MECHANICAL PROVISOS.
 NORTON MUSEUM OF ART
 PERMIT #16050912
 3/9/2017
  
 1) THE MECHANICAL PLANS HAVE BEEN APPROVED
 CONDITIONALLY. A REVISION TO THE PLANS IS REQUIRED TO
 CORRECT THE DEFICIENCIES LISTED BELOW.
  
 A) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN SYSTEMS
 OF THE AHU'S.
  
 B) PROVIDE FIRE DAMPERS FOR ALL DUCTS PENETRATING THE
 FIRE-RATED WALL OF MECHANICAL ROOM 302.
  
 C) A NEW CHILLER (CH-1) IS BEING INSTALLED IN THE
 EXISTING MECHANICAL ROOM. ADDITIONAL VENTILATION FOR
 NORMAL AND EMERGENCY VENTILATION MAY BE REQUIRED. REFER
 TO SECTIONS 1105.6- 1105.6.3.2 FBC-14 MECHANICAL AND
 PROVIDE EXHAUST VENTILATION CALCULATIONS FOR BOTH
 NORMAL AND EMERGENCY CONDITIONS AS REQUIRED BY SECTIONS
 1105.6.3.1 AND 1105.6.3.2. SHOW LOCATIONS OF ALL
 COMPONENTS OF THE VENTILATION SYSTEM INCLUDING EXHAUST
 FANS AND AIR INTAKES. INCLUDE EQUIPMENT SCHEDULES FOR
 ALL EXISTING FANS OR NEW FANS (EXHAUST OR INTAKE)
 INDICATING THEIR CAPACITIES, AND THE DIMENSIONS OF ALL
 AIR INTAKE OPENINGS. PLEASE NOTE THE NEW CH-3 USES A
 DIFFERENT REFRIGERANT THAN THE EXISTING CH-1 AND CH-2,
 THEREFORE THE EXISTING LEAK DETECTOR MAY NOT BE
 COMPATIBLE.
 SUBMIT SPECIFICATIONS FOR THE LEAK DETECTOR.
  
 D) AHU HEATING COIL: CORRECT OR CLARIFY THE CONFLICTS
 BETWEEN THE AC CALCULATIONS FOR THE HEATING COIL
 SELECTION VERSUS THE HEATING CAPACITIES SHOWN IN THE
 EQUIPMENT SCHEDULES: AHU'S 3, 14, 18, 19, 20, & 22.
  
 2) DEFERRED SUBMITTALS: AS REQUESTED BY THE CONTRACTOR
 PLEASE REVIEW THE FOLLOWING LIST OF DEFERRED
 SUBMITTALS. PLEASE NOTE:) DEFERRED SUBMITTALS SECTION
 107.3.4.2 WPB AMENDMENTS TO THE FBC. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 A) STRUCTURAL ENGINEERING FOR INSTALLATION OF THE
 COOLING TOWERS INCLUDING THE SUPPORT BASE, ACCESS
 STAIRS, WALKWAYS AND PLATFORM.
  
 B) MECHANICAL AND ELECTRICAL POWER AND LIGHTING SYSTEMS
 COMMISSIONING: PRELIMINARY AND FINAL REPORTS.
  
 C) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR LOUVERS PROTECTING OUTSIDE AIR AND EXHAUST OUTLET
 OPENINGS. PLEASE NOTE:) PRODUCT APPROVALS- THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 D) MANUFACTURER'S SPECIFICATIONS FOR THE GLOBAL PLASMA
 SOLUTIONS IAQ EQUIPMENT AND DEVICES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  