2017-03-04 08:23:45 | BUILDING PLAN REVIEW |
| NORTON MUSEUM |
| W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| ADD: 1451 S. OLIVE AVE. |
| CONT: GILBANE |
| TEL: 561-236-7052 |
| E-MAIL: [email protected] MICHAEL IZZO |
| E-MAIL: [email protected] MICHAEL J BEAUMIER |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 4TH REVIEW |
| DATE: SAT. 04/ 2017 |
| ACTION: APPROVED / BUILDING PROVISO |
| |
| NOTICE: ROBERT BROWN HAS WRITTEN A LETTER OF APPROVAL |
| FOR ALTERNATE MATERIALS AND DESIGN. E-MAIL MAY 04/2015 |
| AND DESIGN MEETING FROM TUES. JUNE 09/2015 WOULD |
| REQUIRE ALTERNATE MATERIALS AND DESIGN METHODS, |
| (PROPOSED COMPLIANCE METHOD), ERIC H. COTE SENIOR |
| TECHNICAL ADVISOR. |
| |
| **THE TYPE IB CONSTRUCTION CLASSIFICATION IS BASED ON |
| THE TOTAL COMBINED HEIGHT AND AREA OF ALL |
| EXISTING-TO-REMAIN BUILDING PORTIONS+ PROPOSED |
| ADDITIONS, INCLUDING PLANNED FUTURE ADDITIONS. |
| ** THE MATERIALS OF CONSTRUCTION AND ASSOCIATED FIRE |
| RESISTANCE RATINGS OF THE EXISTING TO REMAIN BUILDING |
| PORTIONS WILL REMAIN UNCHANGED (I.E., PREDOMINATELY |
| TYPE IIA, PROTECTED NONCOMBUSTIBLE CONSTRUCTION, OR |
| BETTER, EXCEPT FOR EXISTING ROOF CONSTRUCTION IN THE |
| CIRCA 1940-1942 PORTIONS). |
| ** THE NEW AND EXISTING-TO-REMAIN BUILDING PORTIONS |
| WILL FUNCTION AS A SINGLE BUILDING IN ALL RESPECTS. |
| |
| |
| 1) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER |
| AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO |
| THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014 |
| ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING |
| ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS |
| PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH |
| 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000 |
| EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE |
| IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM |
| LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN |
| ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS |
| PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7. |
| PLATFORM |
| LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE |
| INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER |
| SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO |
| SERVE AS A PART OF A MEANS OF EGRESS. |
| |
| 2) PROVISO: 2014FBC-ACCESSIBLITY CODE 703.4.1 HEIGHT |
| ABOVE FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON |
| SIGNS SHALL BE LOCATED 48 INCHES (1220 MM) MINIMUM |
| ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM |
| THE BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 |
| INCHES (1525 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| HIGHEST TACTILE CHARACTER. |
| |
| 3) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014 |
| FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS |
| VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE |
| REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10). |
| |
| 4) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET |
| 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED |
| PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL |
| DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER |
| COMPONENT, SHOW COMPLIANCE WITH FBC-B 603. |
| |
| 5) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL |
| AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR |
| FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE |
| PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS |
| SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS |
| ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN |
| ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2 SHALL BE |
| USED. |
| |
| 6) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN |
| EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS |
| WOULD BE COVERED UNDER THE BUILDING PERMIT. |
| |
| 7) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO |
| WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL |
| SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL |
| & PLUMBING DISCIPLES. |
| |
| 8) COMPLIED. PRESSURES : SHEETS S008, S009, & S010. |
| |
| 9) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| |
| 10) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| |
| 11) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL |
| IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 12) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| FLORIDA ARCHITECT OR ENGINEER. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND |
| DESIGN DATA. |
| |
| 13) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 14) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET |
| (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| |
| 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| ON THE MECHANICAL EQUIPMENT SCREEN. |
| |
| 16) PROVISO: TYPE IB & IIA BUILDING REQUIRE FIRE |
| RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601 |
| OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS |
| SECTION OF THE CODE. FIRE PROTECTION SHOP DRAWING ARE |
| TO BE PREPARED TO MEET TABLE 6501 OF THE 2014 FBC-B BY |
| G. C. AND SUBMITTED TO THE DESIGNER OF RECORD FOR |
| REVIEW AND APPROVAL BEFORE BEING SUBMITTED TO THE |
| BUILDING DEPARTMENT. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |