Plan Review Notes
Plan Review Notes For Permit 16050912
Permit Number 16050912
Review Stop M
Sequence Number 3
Notes
Date Text
2017-01-10 17:47:303RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16050912
 NORTON MUSUEM
 1/10/17
  
 1) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS.
  
 2) THE REVISED ENERGYGAUGE COMPLIANCE FORM WAS
 SUBMITTED WITHOUT THE OWNER/AGENT'S SIGNATURE.
  
 3) 3RD REQUEST FOR COMPLETE VENTILATION CALCULATIONS.
 THE CALCULATIONS ON M607 ARE FOR THE ROOMS AND SPACES
 UTILIZING THE IAQ PROCEDURE - SYSTEMS 3, 18, 19,20,21,&
 22, HOWEVER MINIMUM VENTILATION CALCULATIONS ARE
 REQUIRED FOR ALL OF THE OTHER ROOMS AND SPACES I.E. THE
 FIRST FLOOR GALLERIES AND DINING AREAS ON THE SOUTH
 END- SYSTEMS 14 & 15. PLEASE NOTE THAT DEMAND
 CONTROLLED VENTILATION MAY BE REQUIRED- SEE SECTION
 C403.2.5.1 FBC-14 ENERGY CONSERVATION.
  
 4) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR
 THE CHILLER ROOM , AND AN EQUIPMENT SCHEDULE FOR EF-9.
  
 5) 3RD REQUEST FOR DUCT SMOKE DETECTORS TO BE SHOWN IN
 THE RETURN AIR SYSTEMS OF THE AHU'S.
  
 6) 3RD REQUEST TO SHOW THE MISSING SMOKE AND FIRE
 DAMPERS:
 REFER TO SECTION 607.5.4.AND PROVIDE SMOKE DAMPERS FOR
 ALL DUCTS LISTED BELOW THAT PENETRATE SMOKE BARRIERS,
 UNLESS MEETING ONE OF THE THREE EXCEPTIONS LISTED UNDER
 THE SECTION.
 M121.5- 12X10 DUCT AT SMITH GALLERY 131/RESTROOM WALL.
 M121.8- 38X14 & 42X14 DUCTS AT LAUDER RESTAURANT
 120/LOBBY 118/CORRIDOR 113 WALLS.
 M122.8- 12X12 AT CONFERENCE 223/MCGRAW 225.
 30X12 AT MCGRAW 225/VESTIBULE 226.
 14X10 AT MARDEN 226/MCGRAW 225.
 M123.7- ALL DUCTS TRAVERSING THROUGH THE MARDEN GALLERY
 226/ CLASSROOM 221/ THE ADMISSIONS/GRAND HALL/& OFFICES
 209 & 210.
 M123.8- DUCTS AT CORRIDOR 301/MEP & GROSS GALLERY 304.
 M123.8:FSD'S FOR DUCTS PENETRATING THE SHAFT AT
 CORRIDOR 301.
 PROVIDE KEY NOTES AT ALL FD, FSD, AND SD DAMPER
 LOCATIONS.
 .
 7) INDICATE HOW ACCESS WILL BE PROVIDED TO THE FIRE
 DAMPERS LOCATED AT THE FLOOR/CEILING ASSEMBLY ABOVE THE
 STILLER AUDITORIUM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 CCOLE
  