Plan Review Notes
Plan Review Notes For Permit 16050912
Permit Number 16050912
Review Stop B
Sequence Number 3
Notes
Date Text
2017-01-23 13:57:50BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JAN. 23/ 2017
 ACTION: DENIED
  
 NOTICE: ROBERT BROWN HAS WRITTEN A LETTER OF APPROVAL
 FOR ALTERNATE MATERIALS AND DESIGN. E-MAIL MAY 04/2015
 AND DESIGN MEETING FROM TUES. JUNE 09/2015 WOULD
 REQUIRE ALTERNATE MATERIALS AND DESIGN METHODS,
 (PROPOSED COMPLIANCE METHOD), ERIC H. COTE SENIOR
 TECHNICAL ADVISOR.
  
 1) COMPLIED.
  
 2) COMPLIED UNDER THE STRUCTURAL ONLY PERMIT 16080215,
 GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014.
  
 4A-H) COMPLIED.
  
 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER
 AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO
 THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014
 ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING
 ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS
 PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000
 EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE
 IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM
 LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN
 ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS
 PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7.
 PLATFORM
 LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE
 INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER
 SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO
 SERVE AS A PART OF A MEANS OF EGRESS.
  
 4J) PROVISO: 2014FBC-ACCESSIBLITY CODE 703.4.1 HEIGHT
 ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
  
  
  
  
 5A) COMPLIED.
  
 5B) 3RD REQUEST. TO CONSIDER THE EXIT PASSAGE WAY
 INDICATED AS CORRIDOR 101M TO BE AN EXTENSION OF THE
 VERTICAL EXIT, THERE WILL NEED TO HAVE A CUT SECTION
 THROUGH THE EXIT ACCESS CORRIDOR (EXIT PASSAGEWAY) EAST
 WEST THAT SHOWS THE FLOOR/ CEILING ASSEMBLIES BELOW AND
 ABOVE WITH THE RATING OF NOT ONLY THE HORIZONTAL
 ASSEMBLIES BUT OF THE VERTICAL SUPPORTING FRAMING. EXIT
 PASSAGEWAYS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711 OR BOTH. SINCE THERE IS
 ROOMS EITHER BELOW OR ABOVE THE EXIT PASSAGEWAY WILL
 NEED TO HAVE THE SAME RATING AS THE VERTICAL EXIT. THIS
 IS NOT CONSIDERED AN EXTENSION TO A STAIRWAY (EXIT
 PASSAGEWAY) IN SECTION 1022.3.1 A FIRE DOOR ASSEMBLY
 COMPLYING WITH SECTION 716.5 SHALL BE INSTALLED IN THE
 FIRE BARRIER TO PROVIDE A MEANS OF EGRESS FROM THE
 INTERIOR EXIT STAIRWAY TO THE EXIT PASSAGEWAY. THE DOOR
 PROTECTS THE VERTICAL EXIT FROM SMOKE AND FIRE. THIS
 REQUEST IS NOT ONLY FROM THE PLAN REVIEWER BUT ALSO THE
 BUILDING OFFICIAL ROBERT BROWN.
  
 2ND ROUND OF COMMENTS. RESPONSE INDICATES THE ENCLOSURE
 THAT CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT
 ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER
 THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS
 SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND
 DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN
 WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11
 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION.
  
 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A
 VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR
 CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE
 VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN
 EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS
 CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT.
 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND
 RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH
 THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
  
 6A) COMPLIED. 6B) EXISTING CONDITION.
  
 6C-G) COMPLIED.
  
 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014
 FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS
 VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE
 REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10).
  
 6I-6J) COMPLIED.
  
 7) COMPLIED.
 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS,
 WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510
 DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT
 AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS
 IN ACCORDANCE WITH NFPA 13.
  
 9) COMPLIED.
  
 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET
 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED
 PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL
 DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER
 COMPONENT, SHOW COMPLIANCE WITH FBC-B 603.
  
 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO
 BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL
 AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR
 FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE
 PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS
 SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS
 ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
  
 13 & 14) COMPLIED.
  
 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS
 WOULD BE COVERED UNDER THE BUILDING PERMIT.
  
 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO
 WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL
 SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL
 & PLUMBING DISCIPLES.
  
 17) COMPLIED. PRESSURES : SHEETS S008, S009, & S010.
  
 18) COMPLIED SEE STRUCTURAL PERMIT: 16080215.
  
 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
  
 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A
 FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 25) 2ND REQUEST TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. CLARIFICATION. PLEASE PROVIDE HOW
 CODE COMPLIANCE WILL BE ACHIEVED, USING WHAT METHODS
 AND MATERIALS. A SPECIFICATION IS JUST THAT, PLEAS
 PROVIDE THE DOCUMENTS HOW THE FIRE RATING OF STRUCTURAL
 MEMBERS WILL BE ACHIEVED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. THANK YOU.
  
 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  