Date |
Text |
2016-10-27 14:47:02 | 2ND REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: 2ND REQUEST |
| |
| 1.NOT COMPLIED. IT APPEARS THAT THE FIXTURE COUNT IS TO |
| LOW FOR THE OCCUPANT LOAD. PLEASE PROVIDE A BREAKDOWN |
| OF FIXTURES REQUIRED AND FIXTURES PROVIDED. PER FBC PL |
| TABLE 403.1 |
| USING THE OCCUPANT LOAD FROM THE LIFE SAFETY PAGES THE |
| REQUIRED NUMBER OF WATER CLOSETS FOR THE WOMEN WOULD BE |
| 26 TOTAL I CAN ONLY FIND 16 ON THE PLAN. THE REQUIRED |
| NUMBER OF WATER CLOSETS FOR THE MEN IS 16 I FOUND 12 ON |
| THE PLAN. IF YOU PROVIDE A BREAKDOWN SHOWING OCCUPANT |
| LOAD FOR EACH OCCUPANT TYPE AND THE REQUIRED FIXTURE |
| COUNT AND WHAT IS PROVIDED> IT MIGHT CLARIFY THIS |
| PROBLEM. |
| |
| 3. NOT COMPLIED SHT. P101-104 PLEASE IDENTIFY PIPING |
| AND SIZES. PERWPB AMEND. TO FBC 107.2.1 |
| |
| 6. NOT COMPLIED PROVIDE ISOMETRIC RISER DIAGRAM FOR ANY |
| NEW STORM WITH SQFT. THAT IS BEING DRAINED ON EACH |
| PIPE. PER WPB AMEND. TO FBC 107.3.5.1.3(13) |
| SHT. P505 |
| A) THEIR ARE PIPES ON THE RISER DIAGRAM THAT END WITH |
| NO INDICATION OF WHERE THEY GO OR WHAT SIZE PLEASE |
| IDENTIFY EACH PEACE OF PIPE TO COINCIDE WITH A LOCATION |
| . |
| B) PROVIDE SQUARE FOOTAGE AND SLOPE ON EACH SECTION OF |
| PIPE. |
| C) SHOW LEVEL AND LOCATION OF EACH ROOF DRAIN. |
| |
| 11.NOT COMPLIED SHT A703 DETAIL 3A SHOW GRAB BARS IN |
| AMBULATORY TOILET COMPARTMENT.PER FBC ACC. 604.8.2.3 |
| |
| NEW COMMENTS: |
| |
| 1. SHT. P504 THE VENTS ON THE FLOOR SINKS CAN NOT RUN |
| HORIZONTALLY. PER FBC PL SEC 905.3 VENT CONNECTION TO |
| DRAINAGE SYSTEM. |
| EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| PIPE. |
| |
| 905.4 VERTICAL RISE OF VENT. |
| EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| |
| 2.SHT. P121.5-P123.8 WHAT ARE THE SYMBOLS OF THE |
| CIRCLES WITH THE P50-P58 PLEASE SHOW ON THE PLAN. PER |
| WPB AMEND. TO FBC 107.2.1 |
| |
| 3. ON THE SANITARY RISER DIAGRAM PLEASE PROVIDE A WAY |
| TO IDENTIFY THE STACKS TO COINCIDE WITH THE FLOOR |
| PLANS. PER WPB AMEND. TO FBC 107.2.1 |
| |
| 4. PROVIDE A ISOMETRIC RISER DIAGRAM FOR THE KITCHEN |
| PLUMBING.. PER WPB AMEND. TO FBC 107.2.1 |
| |
| 5. PLEASE EXPAND OR ENLARGE ALL ISOMETRIC DRAWINGS TO |
| INSURE THAT THEY CAN BE EASILY READ BY THE INSPECTORS |
| IN THE FIELD. PER WPB AMEND. TO FBC 107.2.1 |
| |
| |
| DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |
| |
| |
| |
| |
| |
| |