Plan Review Notes
Plan Review Notes For Permit 16050912
Permit Number 16050912
Review Stop P
Sequence Number 2
Notes
Date Text
2016-10-27 14:47:022ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1.NOT COMPLIED. IT APPEARS THAT THE FIXTURE COUNT IS TO
 LOW FOR THE OCCUPANT LOAD. PLEASE PROVIDE A BREAKDOWN
 OF FIXTURES REQUIRED AND FIXTURES PROVIDED. PER FBC PL
 TABLE 403.1
 USING THE OCCUPANT LOAD FROM THE LIFE SAFETY PAGES THE
 REQUIRED NUMBER OF WATER CLOSETS FOR THE WOMEN WOULD BE
 26 TOTAL I CAN ONLY FIND 16 ON THE PLAN. THE REQUIRED
 NUMBER OF WATER CLOSETS FOR THE MEN IS 16 I FOUND 12 ON
 THE PLAN. IF YOU PROVIDE A BREAKDOWN SHOWING OCCUPANT
 LOAD FOR EACH OCCUPANT TYPE AND THE REQUIRED FIXTURE
 COUNT AND WHAT IS PROVIDED> IT MIGHT CLARIFY THIS
 PROBLEM.
  
 3. NOT COMPLIED SHT. P101-104 PLEASE IDENTIFY PIPING
 AND SIZES. PERWPB AMEND. TO FBC 107.2.1
  
 6. NOT COMPLIED PROVIDE ISOMETRIC RISER DIAGRAM FOR ANY
 NEW STORM WITH SQFT. THAT IS BEING DRAINED ON EACH
 PIPE. PER WPB AMEND. TO FBC 107.3.5.1.3(13)
 SHT. P505
 A) THEIR ARE PIPES ON THE RISER DIAGRAM THAT END WITH
 NO INDICATION OF WHERE THEY GO OR WHAT SIZE PLEASE
 IDENTIFY EACH PEACE OF PIPE TO COINCIDE WITH A LOCATION
 .
 B) PROVIDE SQUARE FOOTAGE AND SLOPE ON EACH SECTION OF
 PIPE.
 C) SHOW LEVEL AND LOCATION OF EACH ROOF DRAIN.
  
 11.NOT COMPLIED SHT A703 DETAIL 3A SHOW GRAB BARS IN
 AMBULATORY TOILET COMPARTMENT.PER FBC ACC. 604.8.2.3
  
 NEW COMMENTS:
  
 1. SHT. P504 THE VENTS ON THE FLOOR SINKS CAN NOT RUN
 HORIZONTALLY. PER FBC PL SEC 905.3 VENT CONNECTION TO
 DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
  
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 2.SHT. P121.5-P123.8 WHAT ARE THE SYMBOLS OF THE
 CIRCLES WITH THE P50-P58 PLEASE SHOW ON THE PLAN. PER
 WPB AMEND. TO FBC 107.2.1
  
 3. ON THE SANITARY RISER DIAGRAM PLEASE PROVIDE A WAY
 TO IDENTIFY THE STACKS TO COINCIDE WITH THE FLOOR
 PLANS. PER WPB AMEND. TO FBC 107.2.1
  
 4. PROVIDE A ISOMETRIC RISER DIAGRAM FOR THE KITCHEN
 PLUMBING.. PER WPB AMEND. TO FBC 107.2.1
  
 5. PLEASE EXPAND OR ENLARGE ALL ISOMETRIC DRAWINGS TO
 INSURE THAT THEY CAN BE EASILY READ BY THE INSPECTORS
 IN THE FIELD. PER WPB AMEND. TO FBC 107.2.1
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved