Plan Review Notes
Plan Review Notes For Permit 16050912
Permit Number 16050912
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-29 10:24:36BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. 29/ 2016
 ACTION: DENIED
  
 NOTICE: ROBERT BROWN IS SUPPOSE TO WRITE A LETTER OF
 APPROVAL FOR ALTERNATE MATERIALS AND DESIGN.
  
 1) COMPLIED.
  
 2) 2ND REQUEST, NOT COMPLETED UNDER THE FOUNDATION/
 STRUCTURE ONLY PERMIT. SHEET 0277_S003 HEADING
 FOUNDATIONS INDICATES THERE WAS A GEOTECHNICAL REPORT
 COMPLETED BY ARDAMAN 12/16/2014. PLEASE SUBMIT REPORT.
 NOTE WHEN SUBMITTED ELECTRONICALLY THE SOILS ENGINEER
 WILL NEED TO SUBMIT UNDER AN ELECTRONIC SEAL PER
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS (ELECTRONIC SEALS).
 OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT
 WILL BE RETAINED AND SCANNED INTO THE SYSTEM.
 PLEASE NOTE THE RESPONSE UNDER THE STRUCTURE ONLY
 PERMIT WAS THAT A PAPER COPY WAS ALREADY SUBMITTED TO
 THE BUILDING DEPARTMENT. I?VE CHECKED WITH THE
 ELECTRONIC PLAN REVIEW LIBRARIAN ON THE INCOMING
 APPLICATION AND ASSORTED PAPERWORK, THERE IS NO PAPER A
 GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014
 WITHIN THE PAPERWORK, THE LIBRARIAN RECORDS SUCH PAPER
 DOCUMENTS SO I KNOW TO VERIFY THE REPORT IN PAPER IS
 THE SAME REPORT SUBMITTED ELECTRONICALLY AND VERIFY
 SIGNATURE ON THE PAPER DOCUMENT.
  
 4A-H) COMPLIED.
  
 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER
 AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO
 THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014
 ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING
 ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS
 PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000
 EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE
 IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM
 LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN
 ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS
 PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7.
 PLATFORM
 LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE
 INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER
 SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO
 SERVE AS A PART OF A MEANS OF EGRESS.
  
 4J) 2ND REQUEST. THE ISSUE IS WITH EXITING, AND AN
 ACCESSIBLE EXIT, NOT JUST FOR THIS ROOM BUT EXITS FOR
 THE WHOLE OF THE BUILDING. THE DRAWING INDEX INDICATES
 SHEET 0260.03_A933_SIGNAGE DETAILS . THE ARE NO DETAILS
 FOR ACCESSIBLE SIGNAGE AND FOR DOORS THAT ARE NOT PART
 OF AN ACCESSIBLE ROUTE. THE HEIGHT OF SIGNAGE THAT HAS
 TACTILE CHARACTERS WITH BRAILLE,2014 FBC-ACCESSIBILITY
 CODE 703.4.1.
 703.1 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL
 AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN
 WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
 2014 FBC-B 1011.4 RAISED CHARACTER AND BRAILLE EXIT
 SIGNS. A SIGN STATING EXIT IN RAISED CHARACTERS AND
 BRAILLE AND COMPLYING WITH ICC A117.1 SHALL BE PROVIDED
 ADJACENT TO EACH DOOR TO AN AREA OF REFUGE, AN EXTERIOR
 AREA FOR ASSISTED RESCUE, AN EXIT STAIRWAY, AN EXIT
 RAMP, AN EXIT PASSAGEWAY AND THE EXIT DISCHARGE.
  
 1ST ROUND COMMENTS. THE SOME OF THE EXITS DO NOT
 INDICATE IF THEY ARE ACCESSIBLE EGRESS DOORWAYS
 COMPLYING WITH 2014 FBC-ACCESSIBILITY CODE 207.1
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE 2003
 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE
 MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1
 FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL BE
 SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
 THE LIFE SAFETY PLAN IS VAGUE AT BEST. 1027.5 ACCESS TO
 A PUBLIC WAY. THE EXIT DISCHARGE SHALL PROVIDE A DIRECT
 AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY.
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. RESPONSE INDICATES THE ENCLOSURE THAT
 CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT
 ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER
 THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS
 SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND
 DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN
 WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11
 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION.
  
 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A
 VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR
 CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE
 VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN
 EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS
 CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT.
 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND
 RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH
 THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
  
 6A) COMPLIED. 6B) EXISTING CONDITION.
  
 6C-G) COMPLIED.
  
 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014
 FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS
 VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE
 REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10).
  
 6I-6J) COMPLIED.
  
 7) COMPLIED.
 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS,
 WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510
 DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT
 AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS
 IN ACCORDANCE WITH NFPA 13.
  
 9) COMPLIED.
  
 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET
 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED
 PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL
 DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER
 COMPONENT, SHOW COMPLIANCE WITH FBC-B 603.
  
 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO
 BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL
 AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR
 FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE
 PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS
 SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS
 ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
  
 13 & 14) COMPLIED.
  
 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN
 EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS
 WOULD BE COVERED UNDER THE BUILDING PERMIT.
  
 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO
 WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL
 SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL
 & PLUMBING DISCIPLES.
  
 17) SEMI-COMPLIED. THE SHEETS S008, S009, & S010 ALL
 SHOW THE PRESSURES FROM THE WIND STUDY FOR ROOF ZONES
 1, 2 & 3. THESE 3 SHEETS LISTED ABOVE S008 IS THE ONLY
 SHEET WHICH SHOWS PRESSURES FOR ROOF ZONES 1, 2 & 3.
 THE ROOF ZONES DO NOT PROVIDE PRESSURES FOR ROOF TOP
 EQUIPMENT THAT WILL BE ANCHORED TO THE (MWFRS) MAIN
 WIND FORCE RESISTING SYSTEM.
 PLEASE PROVIDE THE PRESSURES FOR THE DOORS AND WINDOWS
 IN WALL ZONES 4 & 5. PLEASE PROVIDE THE PRESSURES FOR
 THE WINDOWS AND DOORS AS PER THE WIND STUDY THAT WAS
 COMPLETED. FBC-B 1609.1.1DETERMINATION OF WIND LOADS.
 EXCEPTION #6 WIND TUNNEL TESTING IN ACCORDANCE WITH
 CHAPTER 31 OF ASCE 7. PLEASE NOTE THIS MAY ALSO BE
 ACCOMPLISHED UNDER THE STRUCTURE ONLY PERMIT #
 16080215.
 18) 2ND REQUEST. IT SEEMS THE PLANS ARE INCOMPLETE
 PLEASE PROVIDE WHERE THE FOUNDATION SCHEDULE, CONCRETE
 COLUMN, HOOPS & VERTICAL REBAR AND BEAMS ARE LOCATED, I
 COULD NOT FIND THEM IN THE STRUCTURAL SHEETS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS/ BUILDING:
 FOUNDATION SCHEDULE
 COLUMN SCHEDULE
 BEAM ( CONCRETE/ LINTEL) SCHEDULE
  
 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
  
 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A
 FLORIDA ARCHITECT OR ENGINEER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE
 SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE
 SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 25) NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE
 RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601
 OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS
 SECTION OF THE CODE. THANK YOU.
  
 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  