2016-10-29 10:24:36 | BUILDING PLAN REVIEW |
| NORTON MUSEUM |
| W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| ADD: 1451 S. OLIVE AVE. |
| CONT: GILBANE |
| TEL: 561-236-7052 |
| E-MAIL: [email protected] MICHAEL IZZO |
| E-MAIL: [email protected] MICHAEL J BEAUMIER |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SAT. 29/ 2016 |
| ACTION: DENIED |
| |
| NOTICE: ROBERT BROWN IS SUPPOSE TO WRITE A LETTER OF |
| APPROVAL FOR ALTERNATE MATERIALS AND DESIGN. |
| |
| 1) COMPLIED. |
| |
| 2) 2ND REQUEST, NOT COMPLETED UNDER THE FOUNDATION/ |
| STRUCTURE ONLY PERMIT. SHEET 0277_S003 HEADING |
| FOUNDATIONS INDICATES THERE WAS A GEOTECHNICAL REPORT |
| COMPLETED BY ARDAMAN 12/16/2014. PLEASE SUBMIT REPORT. |
| NOTE WHEN SUBMITTED ELECTRONICALLY THE SOILS ENGINEER |
| WILL NEED TO SUBMIT UNDER AN ELECTRONIC SEAL PER |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS (ELECTRONIC SEALS). |
| OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT |
| WILL BE RETAINED AND SCANNED INTO THE SYSTEM. |
| PLEASE NOTE THE RESPONSE UNDER THE STRUCTURE ONLY |
| PERMIT WAS THAT A PAPER COPY WAS ALREADY SUBMITTED TO |
| THE BUILDING DEPARTMENT. I?VE CHECKED WITH THE |
| ELECTRONIC PLAN REVIEW LIBRARIAN ON THE INCOMING |
| APPLICATION AND ASSORTED PAPERWORK, THERE IS NO PAPER A |
| GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014 |
| WITHIN THE PAPERWORK, THE LIBRARIAN RECORDS SUCH PAPER |
| DOCUMENTS SO I KNOW TO VERIFY THE REPORT IN PAPER IS |
| THE SAME REPORT SUBMITTED ELECTRONICALLY AND VERIFY |
| SIGNATURE ON THE PAPER DOCUMENT. |
| |
| 4A-H) COMPLIED. |
| |
| 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER |
| AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO |
| THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014 |
| ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING |
| ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS |
| PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH |
| 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000 |
| EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE |
| IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM |
| LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN |
| ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS |
| PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7. |
| PLATFORM |
| LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE |
| INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER |
| SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO |
| SERVE AS A PART OF A MEANS OF EGRESS. |
| |
| 4J) 2ND REQUEST. THE ISSUE IS WITH EXITING, AND AN |
| ACCESSIBLE EXIT, NOT JUST FOR THIS ROOM BUT EXITS FOR |
| THE WHOLE OF THE BUILDING. THE DRAWING INDEX INDICATES |
| SHEET 0260.03_A933_SIGNAGE DETAILS . THE ARE NO DETAILS |
| FOR ACCESSIBLE SIGNAGE AND FOR DOORS THAT ARE NOT PART |
| OF AN ACCESSIBLE ROUTE. THE HEIGHT OF SIGNAGE THAT HAS |
| TACTILE CHARACTERS WITH BRAILLE,2014 FBC-ACCESSIBILITY |
| CODE 703.4.1. |
| 703.1 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL |
| AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN |
| WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO |
| SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE |
| CHARACTERS, SHALL BE PROVIDED. |
| 2014 FBC-B 1011.4 RAISED CHARACTER AND BRAILLE EXIT |
| SIGNS. A SIGN STATING EXIT IN RAISED CHARACTERS AND |
| BRAILLE AND COMPLYING WITH ICC A117.1 SHALL BE PROVIDED |
| ADJACENT TO EACH DOOR TO AN AREA OF REFUGE, AN EXTERIOR |
| AREA FOR ASSISTED RESCUE, AN EXIT STAIRWAY, AN EXIT |
| RAMP, AN EXIT PASSAGEWAY AND THE EXIT DISCHARGE. |
| |
| 1ST ROUND COMMENTS. THE SOME OF THE EXITS DO NOT |
| INDICATE IF THEY ARE ACCESSIBLE EGRESS DOORWAYS |
| COMPLYING WITH 2014 FBC-ACCESSIBILITY CODE 207.1 |
| ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE 2003 |
| IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE |
| MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1 |
| FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL BE |
| SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. |
| THE LIFE SAFETY PLAN IS VAGUE AT BEST. 1027.5 ACCESS TO |
| A PUBLIC WAY. THE EXIT DISCHARGE SHALL PROVIDE A DIRECT |
| AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY. |
| |
| 5A) COMPLIED. |
| |
| 5B) 2ND REQUEST. RESPONSE INDICATES THE ENCLOSURE THAT |
| CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT |
| ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER |
| THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS |
| SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND |
| DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN |
| WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA |
| BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11 |
| ALTERNATE MATERIALS, DESIGN AND METHODS OF |
| CONSTRUCTION. |
| |
| 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A |
| VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR |
| CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE |
| VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN |
| EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS |
| CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT. |
| 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND |
| RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH |
| THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5. |
| OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER |
| THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO |
| THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM |
| NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE |
| ENCLOSURE. |
| |
| 6A) COMPLIED. 6B) EXISTING CONDITION. |
| |
| 6C-G) COMPLIED. |
| |
| 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014 |
| FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS |
| VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE |
| REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10). |
| |
| 6I-6J) COMPLIED. |
| |
| 7) COMPLIED. |
| 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS, |
| WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510 |
| DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT |
| AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS |
| IN ACCORDANCE WITH NFPA 13. |
| |
| 9) COMPLIED. |
| |
| 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET |
| 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED |
| PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL |
| DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER |
| COMPONENT, SHOW COMPLIANCE WITH FBC-B 603. |
| |
| 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO |
| BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL |
| AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR |
| FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE |
| PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS |
| SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS |
| ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN |
| ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE |
| USED. |
| |
| 13 & 14) COMPLIED. |
| |
| 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN |
| EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS |
| WOULD BE COVERED UNDER THE BUILDING PERMIT. |
| |
| 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO |
| WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL |
| SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL |
| & PLUMBING DISCIPLES. |
| |
| 17) SEMI-COMPLIED. THE SHEETS S008, S009, & S010 ALL |
| SHOW THE PRESSURES FROM THE WIND STUDY FOR ROOF ZONES |
| 1, 2 & 3. THESE 3 SHEETS LISTED ABOVE S008 IS THE ONLY |
| SHEET WHICH SHOWS PRESSURES FOR ROOF ZONES 1, 2 & 3. |
| THE ROOF ZONES DO NOT PROVIDE PRESSURES FOR ROOF TOP |
| EQUIPMENT THAT WILL BE ANCHORED TO THE (MWFRS) MAIN |
| WIND FORCE RESISTING SYSTEM. |
| PLEASE PROVIDE THE PRESSURES FOR THE DOORS AND WINDOWS |
| IN WALL ZONES 4 & 5. PLEASE PROVIDE THE PRESSURES FOR |
| THE WINDOWS AND DOORS AS PER THE WIND STUDY THAT WAS |
| COMPLETED. FBC-B 1609.1.1DETERMINATION OF WIND LOADS. |
| EXCEPTION #6 WIND TUNNEL TESTING IN ACCORDANCE WITH |
| CHAPTER 31 OF ASCE 7. PLEASE NOTE THIS MAY ALSO BE |
| ACCOMPLISHED UNDER THE STRUCTURE ONLY PERMIT # |
| 16080215. |
| 18) 2ND REQUEST. IT SEEMS THE PLANS ARE INCOMPLETE |
| PLEASE PROVIDE WHERE THE FOUNDATION SCHEDULE, CONCRETE |
| COLUMN, HOOPS & VERTICAL REBAR AND BEAMS ARE LOCATED, I |
| COULD NOT FIND THEM IN THE STRUCTURAL SHEETS. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1.1. COMMERCIAL BUILDINGS/ BUILDING: |
| FOUNDATION SCHEDULE |
| COLUMN SCHEDULE |
| BEAM ( CONCRETE/ LINTEL) SCHEDULE |
| |
| 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| |
| 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL |
| IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| FLORIDA ARCHITECT OR ENGINEER. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND |
| DESIGN DATA. |
| |
| 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET |
| (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| |
| 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| ON THE MECHANICAL EQUIPMENT SCREEN. |
| |
| 25) NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE |
| RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601 |
| OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS |
| SECTION OF THE CODE. THANK YOU. |
| |
| 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |