2016-06-28 14:15:49 | 1ST REVIEW |
| |
| |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| |
| PLUMBING COMMENTS: |
| |
| 1. IT APPEARS THAT THE FIXTURE COUNT IS TO LOW FOR THE |
| OCCUPANT LOAD. PLEASE PROVIDE A BREAKDOWN OF FIXTURES |
| REQUIRED AND FIXTURES PROVIDED. PER FBC PL TABLE 403.1 |
| |
| 2. SEPARATE PERMITS REQUIRED FOR ANY NEW BACKFLOW |
| DEVICES AT METERS. PER WPB UTILITIES |
| |
| 3. SHT. P101-104 PLEASE IDENTIFY PIPING AND SIZES. |
| PERWPB AMEND. TO FBC 107.2.1 |
| |
| 4. SHT. P122.7-123.7-122.8-123.8 THE NOTE ON THE GAS |
| MAIN AND COLD WATER MAIN READS 3IN GAS AND CW THE GAS |
| MAIN IS SHOWN AS 2IN. IN OTHER AREAS PLEASE CLARIFY. |
| PER WPB AMEND. TO FBC 107.2.1 |
| |
| 5. PLEASE PROVIDE SEPARATE SANITARY AND WATER ISOMETRIC |
| DRAWINGS FOR THE KITCHEN, COFFEE BAR AND KITCHENETTE RM |
| 212 PER WPB AMEND. TO FBC 107.3.5.1.3(13) |
| |
| 6. PROVIDE ISOMETRIC RISER DIAGRAM FOR ANY NEW STORM |
| WITH SQFT. THAT IS BEING DRAINED ON EACH PIPE. PER WPB |
| AMEND. TO FBC 107.3.5.1.3(13) |
| |
| 7. SHT. P503 RISER FO RUMENS RM 143 THE URINALS ARE |
| SHOWN AS WC-1 PLEASE CLARIFY. PER WPB AMEND. TO FBC |
| 107.2.1 |
| |
| 8. SHT. 503 SHOW FAMILY BATHROOM ON RISER DIAGRAM. PER |
| WPB AMEND. TO FBC 107.2.1 |
| |
| 9. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR. |
| PER WPB AMEND. TO FBC 107.2.1 |
| |
| 10. SHT. 501 DETAIL 13 PLEASE COMPLY WITH GREASE TRAP |
| DETAIL |
| NOTE |
| 1) INLET INVERT SHALL DISCHARGE A MINIMUM OF 2 ?? ABOVE |
| THE LIQUID LEVEL LINE AND OUTLET PIPE SHALL HAVE A TEE |
| WITH A MINIMUM DIAMETER OF 4? TO WITHIN 8? OF THE |
| BOTTOM OF THE TANK. |
| 2) MANHOLES SHALL BE PROVIDED OVER THE INLET AND OUTLET |
| OF EACH INTERCEPTOR AND BE BROUGHT TO GRADE. MINIMUM |
| SIZE OF MANHOLES SHALL BE 24?. |
| 3) LID TYPE: |
| A) REGULAR ? FOUR-INCH THICK REINFORCED CONCRETE OR |
| APPROVED EQUIVALENT. |
| B) TRAFFIC BEARING ? SIX-INCH THICK REINFORCED CONCRETE |
| OR APPROVED EQUIVALENT. |
| 4) A TWO-WAY CLEANOUT TEE, BROUGHT TO GRADE, SHALL BE |
| INSTALLED ENTERING AND LEAVING EACH GREASE INTERCEPTOR. |
| 5) CLEANOUTS INSTALLED IN VEHICULAR TRAFFIC PAVED AREAS |
| SHALL BE PROTECTED BY USE OF A CLEANOUT BOX WITH METAL |
| LID. |
| 6) WALLS SHALL BE A MINIMUM OF 3? THICK AND BOTTOM |
| SHALL BE A MINIMUM OF 4? THICK REINFORCED CONCRETE. |
| 7) TANK MUST BE TRAFFIC BEARING. |
| 8) PROVIDE ENGINEER OF RECORD APPROVED DETAIL/SHOP |
| DRAWINGS. |
| 9) SIZE: SIZE OF THE GREASE TRAP SHALL BE BASED UPON |
| THE ANTICIPATED FLOW RATE, WATER TEMPERATURE AND GREASE |
| CONCENTRATION. ADEQUATE DETENTION TIME SHALL BE |
| PROVIDED TO ALLOW THE GREASE TO BE DEPOSITED WITHIN THE |
| GREASE TRAP BEFORE ENTERING THE CITY WASTEWATER SYSTEM. |
| MINIMUM CAPACITY SIZE: 750 GALLONS. MAXIMUM CAPACITY |
| SIZE: 1250 GALLONS. |
| FOR SIZE APPROVAL, PLEASE CONTACT THE UTILITIES |
| DEPARTMENT, ENVIRONMENTS COMPLIANCE (HOLLY MCGRATH |
| LABORATORY) SUPERVISOR: (561) 822-2271 E-MAIL: |
| [email protected] |
| 10) ALTERNATE MATERIALS AND DESIGN SHALL BE SUBMITTED |
| FOR INDIVIDUAL APPROVAL. |
| |
| 11. SHT A703 DETAIL 3A SHOW GRAB BARS IN AMBULATORY |
| TOILET COMPARTMENT.PER FBC ACC. 604.8.2.3 |
| |
| |
| DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |
| |
| |
| |
| |
| |