2016-06-20 16:14:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET FS 200 - THERE IS NO INDICATION THAT THE HOOD
 VENTING WILL BE INSTALLED PER NFPA 96 AND UNDER
 SEPARATE SHOP DRAWINGS.
  
 NFPA 101
 CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
  
 PLEASE PROVIDE THE APPLICABLE NOTE.
  
  
 2) SHEET S 300 - THERE APPEARS TO LIGHTWEIGHT TRUSS
 CONSTRUCTION WITHIN AND ON THE STRUCTURE.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 3) SHEET LS 001 & FP 100 - A STANDPIPE SYSTME IS
 INDICATED ON LS 100; HOWEVER, THERE IS NO INDICATIONS
 OF STANDPIPE(S) ON FP 100.
  
 PLEASE PROVIDE INDICATIONS AND LOCATIONS OF STANDPIPE
 PROTECTION.
  
  
 4) SHEET E 001 - THERE IS NO INDICATION THAT THE FIRE
 ALARM WILL BE INSTALLED PER NFPA 72 AND UNDER SEPARATE
 SHOP DRAWINGS.
  
 NFPA 101, CHAPTER 9 BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
 9.6.1.3 A FIRE ALARM SYSTEM REQUIRED FOR LIFE SAFETY
 SHALL BE INSTALLED, TESTED, AND MAINTAINED IN
 ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF N
 FPA 70, NATIONAL ELECTRICAL CODE, AND NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN USE.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE FIRE ALARM
 SHALL BE INSTALLED PER NFPA 72 AND UNDER SEPARATE SHOP
 DRAWINGS..
  
  
 5) SHEET LS 001 - THERE IS NO INDICATIONS THAT THE FIRE
 ALARM WILL BE SUBMITTED AND INSTALLED UNDER SEPARATE
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE.
  
  
 6) SHEET LS 001 - THERE IS INDICATION UNDER THE TILTE
 VERTICAL OPENINGS FOR THE INSTALLTION OF A DRAFT
 CURTAIN AND CLOSELY SPACED SPRINKLERS. SHEET FP 100 AND
 OTHER FP SHEETS DO NOT INCLUDE INDICATIONS OR DESIGN.
  
 PLEASE PROVIDE DESIGN INDICATORS FOR DRAFT CURTAINS AND
 CLOSELY SPACED SPRINKLERS IN THE APPLICABLE SPACES PER
 THE ENGINEER OF RECORD.
  
  
 7) SHEET A 806 - WITHIN THE DOOR SCHEDULE UNDER THE
 HDWR SET HEADING THERE IS REFERENCE TO "E" NUMBERS AND
 OTHER NUMBERS. THOSE INDICATORS COULD NOT BE READILY
 IDENTIFIED ON THIS SHEET OR ANOTHER SHEET TO CONFIRM
 PROPER HARDWARE.
  
 PLEASE CLARIFY OR IDENTFY THE CORRESPONDING SHEET.
  
 8) SHEET LS 101 & A 806 - DOOR 116 IS INDCIATED WITHIN
 A SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE DOES
 NOT INDICATE IT WITH ANY FIRE RATING.
  
 PLEASE CORRECT OR VERIFY.
  
 9) SHEET LS 101 & A 806 - DOOR 118 D IS INDICATED
 WITHINA SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE
 DOES NOT INDICATE IT WITH ANY FIRE RATING.
  
 10) SHEET LS 101 & A 806 - DOOR 123 IS INDICATED WITHIN
 A 2 HR FIRE RATED WALL; HOWEVER, THE DOOR SCHEDULE
 INDICATES AS A SMOKE BARRIER DOOR.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 11) SHEET LS 101, A 121 & A 806 - THE FLOOR LAYOUT
 AROUND DOOR 105 IS SLIGHTLY DIFFERENT; HOWEVER, DOOR
 105 IS WITHIN A 2 HR FIRE RATED WALL AND THE DOOR
 SCHEDULE DOES NOT INDICATE ANY FIRE RATING.
  
 PLEASE CORRECT TO 90 MIN DOOR OR VERIFY.
  
 12) SHEET LS 102 & A 806 - DOOR 226E IS INDICATED
 WITHIN A SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE
 DOES NOT INDICATE IT WITH ANY FIRE RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 13 ) SHEET LS 102 & A 806 - DOOR 225A IS INDICATED
 WITHIN A SMOKE BARRIER WALL; HOWEVER, THE DOOR SCHEDULE
 DOES NOT INDICATE IT WITH ANY FIRE RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 14) SHEET LS 101M & A 806 - DOOR 101 MA IS INDICATED
 WITHIN A 2 HR FIRE RATED WALL; HOWEVER, THE DOOR
 SCHEDULE INDICATES NO RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 15) SHEET LS 101 & A 806 - DOOR 124 IS INDICATED WITHIN
 A 2 HR FIRE RATED WALL; HOWEVER, THE DOOR SCHEDULE
 INDICATES NO RATING.
  
 PLEASE COORECT TO 90 MIN. DOOR OR VERIFY.
  
 16) SHEET LS 101 & A 806 - THE DOOR CONNECTING VESTIBLE
 124 AND THE STAIRWELL DOES NOT APPEAR TO BE INDICATED
 WITH A DOOR NUMBER AND IS NOT ON THE DOOR SCHEDULE.
  
 PLEASE COORECT OR VERIFY.
  
 17) SHEET A 806 - THERE IS INDICATIONS WITHIN THE DOOR
 SCHEDULE OF HARDWARE SET ID NUMBERS. I AM NOT ABLE TO
 READLITY LOCATE THE SHEET THAT IDENTIFIES THE
 CORRESPONDING HARDWARE SETS FOR VERIFICATION PURPOSES.
  
 PLEASE CORRECT OF VERIFY.
  
 18) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL