2016-06-03 19:00:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MAXIMUM WATER VELOCITY IN BRANCH SUCTION PIPING
 IS 6 FEET PER SECOND WHEN ONE OF THE PAIR OF MAIN
 DRAINS IS BLOCKED PER ANSI/APSP-7 2006. THE FLOW RATE
 IN THE 2-1/2" SUCTION PIPE IS 7.64 FPS. THE 1 HP JANDY
 FLOPRO VARIABLE SPEED PUMP HAS A MAXIMUM FLOW RATE OF
 MORE THAN 120 GPM AT 20 FT OF HEAD PER THE PUMP CURVE
 THAT WAS SUBMITTED.
  