2016-05-23 12:50:22WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 (1) AHU #1 - AS PER TRANE DUCULATOR 12"X12" [email protected]
 FRICTION LOST PER 100' IS 850 CFM. PLAN IS SHOWING 2000
 CFM DUMPING INTO A 12"X12" DUCT.
 AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800 CFM. DESIGN
 CFM ON PLANS IS 2000 CFM.
 RETURN AIR GRILL ON PLANS IS A200. AS PER CEILINGOUTLET
 SCHEDULE RETURMN AIR GRILL SHOULD BE D 2000.
 CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (2) AHU #2 - PLANS SHOW RETURN AIR IS 1300CFM. TOTAL
 SUPPLY AIR IS 2800.
 AS PER TRANE DUCULATOR 12"X12" [email protected] FRICTION LOST
 PER 100' IS 850 CFM. PLAN IS SHOWING 2800 CFM DUMPING
 INTO A 12"X12" DUCT.
 CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (3) AHU #3 - PROVIDE RETURN AIR.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (4) AHU #4 - AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800
 CFM. DESIGN CFM ON PLANS IS 2000 CFM.
 DRAWING OF SUPPLY DUCT ON PLANS SHOW PHYSICAL REDUCTION
 IN DUCT SIZES BUT DUCT IS IDENTIFIED AS 18" DUCT
 THROUGHOUT.
 CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (5) AHU #5 - AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800
 CFM. DESIGN CFM ON PLANS IS 2000 CFM.
 PROVIDE ON PLANS RETURN AIR.
 SHOW ALL OUTSIDE AIR DUCTS FOR AHU.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 CHANGE #2 ON EQUIPMENT SCHEDULE TO ALL SMOKE DETECTORS
 WILL BE INSTALLED IN RETURN AIR. (AS PER FBC MECHANICAL
 CODE 2014)
  
  