2016-05-27 14:50:43INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW AND REFLECT ON CONSTRUCTION RECORD
 DRAWINGS, COMPLIANCE WITH FBC ENERGY CONSERVATION 2014
 CODE AND METHOD TO ACHIEVE THE REQUIRED MEANS OF
 CONTROL OF LIGHTING, LIGHTING LEVELS ETC. C405.2.1- 2.4
 2. PLEASE PROVIDE SUFFICIENT INFORMATION REGARDING THE
 EXTENT OF THE ALTERATION. CLARIFY THE EXISTING POWER
 OUTLETS IN RELATION TO THE RELOCATED OR NEW OUTLETS
 BEING INSTALLED. FBC 107.3.5 MINIMUM PLAN REVIEW. NOTE
 THAT SHEET 2.0E AND 2.1E ARE VERY VAGUE AS TO REQUIRED
 CIRCUIT DESIGNATION AND LABELING.
 3. LABEL ALL REQUIRED GFCI PROTECTED OUTLET WITHIN THE
 FOOD PREPARATION AREA AND WITHIN 6FT OF ALL SINKS. NEC
 210.8B
 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS OR
 CONCERNS.
  