Plan Review Notes For Permit 16050779 |
Permit Number |
16050779 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-27 14:50:43 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PLEASE SHOW AND REFLECT ON CONSTRUCTION RECORD | | DRAWINGS, COMPLIANCE WITH FBC ENERGY CONSERVATION 2014 | | CODE AND METHOD TO ACHIEVE THE REQUIRED MEANS OF | | CONTROL OF LIGHTING, LIGHTING LEVELS ETC. C405.2.1- 2.4 | | 2. PLEASE PROVIDE SUFFICIENT INFORMATION REGARDING THE | | EXTENT OF THE ALTERATION. CLARIFY THE EXISTING POWER | | OUTLETS IN RELATION TO THE RELOCATED OR NEW OUTLETS | | BEING INSTALLED. FBC 107.3.5 MINIMUM PLAN REVIEW. NOTE | | THAT SHEET 2.0E AND 2.1E ARE VERY VAGUE AS TO REQUIRED | | CIRCUIT DESIGNATION AND LABELING. | | 3. LABEL ALL REQUIRED GFCI PROTECTED OUTLET WITHIN THE | | FOOD PREPARATION AREA AND WITHIN 6FT OF ALL SINKS. NEC | | 210.8B | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS OR | | CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|