2016-05-31 17:37:23REVISION IS DENIED BY MECHANICAL.
  
 1) THE RETURN DUCT FOR BEDROOM #2 IS UNDER-SIZED. THE
 PLAN HAS A 6" SUPPLY DUCT WITH A 7" RETURN DUCT FOR
 BEDROOM #2. FBCR M1602.4 REQUIRES THE TRANSFER DUCT TO
 BE 1.5 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM.
  
 2) THE LOCATION OF THE CONDENSING UNIT HAS BEEN CHANGED
 ON THE FLOOR PLAN FOR UNIT B ON SHEET A-1.1. PLEASE
 COORDINATE THE DRAWINGS.
  
  
  