Plan Review Notes For Permit 16050773 |
Permit Number |
16050773 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-31 17:37:23 | REVISION IS DENIED BY MECHANICAL. | | | | 1) THE RETURN DUCT FOR BEDROOM #2 IS UNDER-SIZED. THE | | PLAN HAS A 6" SUPPLY DUCT WITH A 7" RETURN DUCT FOR | | BEDROOM #2. FBCR M1602.4 REQUIRES THE TRANSFER DUCT TO | | BE 1.5 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY | | DUCT ENTERING THE ROOM. | | | | 2) THE LOCATION OF THE CONDENSING UNIT HAS BEEN CHANGED | | ON THE FLOOR PLAN FOR UNIT B ON SHEET A-1.1. PLEASE | | COORDINATE THE DRAWINGS. | | | | | | |
|